2003-02-03 00:00:00BUILDING REVIEW CHECKLIST:
 1-A)PROVIDE SITE PLAN DRAWN TO SCALE AND
 WITH DIMENSIONS THAT MATCH SURVEY
 B)SPECIFY BUILDING SIDE SETBACKS ALSO.
 C)WHAT'S FSC SHOWN ON CODE EDITION USED.
 WE USE FLORIDA BUILDING CODE (FBC)2001
 D)BUILDING CODE/WIND LOAD DESIGN CERTIFI
 CATION IS MISSING SOME INFORMATION.
 SEE SEC. 1606.1.7 FBC 2001 FOR ALL
 FIVE ITEMS REQUIRED ON EVERY JOB.
  
 2-PROVIDE SURVEY WITH ORIGINAL SIGNATURE
 AND SEAL AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTES WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS.
 3-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE PLANS AND SEC. 2405.2 FBC 2001.
 4-SPECIFY SIZE OF ATTIC ACCESS. SECTION
 2309.6 FBC 2001.
 5-SPECIFY SIZE OF ATTIC VENTS. SECTION
 2309.7 FBC 2001.
 6-PROVIDE DETAILS/SPECIFICATIONS FOR
 CEILING INSTALLATION AT FRONT AND REAR
 PORCHES. AND SPECIFY FASTENERS SIZE &
 SPACING AS REQUIRED BY ASTM C-926 AND
 ASTM C-1063. SEC. 2504.2 FBC 2001.
 7-CLARIFY WHAT IS SIMPSON LSTA24-4?.
 HOW IS THIS STRAP TIE USED TO CONNECT
 THE WOOD COLUMN TO THE BEAM AT MID AND
 CORNER LOCATIONS? PROVIDE DETAIL. THIS
 TYPE OF CONNECTOR PROVIDES NOT UPLIFT
 AND LATERAL SUPPORT. SEE SIMPSON CAT.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 8-SHEET S-1:
 A)SPECIFY SUPPORTS & SPACING FOR WWM
 IN CONCRETE SLAB. SEE SEC. 1909.3 FBC.
 B)SPECIFY SIZE OF VAPOR BARRIER SEE SEC.
 1909.2 FBC 2001.
 C)SPECIFY FIREBLOCKING IN TYPICAL WALL
 SECTION. SEE SEC. 2305.1.4 FBC 2001.
  
 9-FOOTING SIZE SPECIFIED ON FOUNDATION
 PLAN DOESN'T MATCH SIZE SHOWN ON WALL
 SECTION. REVISE AS REQUIRED.
 10-PROVIDE ROOF FRAMING PLAN SHOWING
 CALCULATED UPLIFT LOADS AND PROVIDE
 TRUSS ANCHOR SCHEDULE AS REQUIRED.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 11-A/C AREA AND UNDER ATTIC AREA SHOWN
 ON THE ENERGY CALCULATIONS DON'T MATCH
 PLANS. REVISE AS REQUIRED. ALSO, WRITE
 SPECIFIC ADDRESS.
 12-PRODUCT APPROVAL FOR EXTERIOR DOORS
 IS EXPIRED. ALSO, CLARIFY IF THIS IS
 THE SAME DOOR FOR ENTRY DOOR,REAR DOOR
 AND STORAGE DOOR. OTHERWISE, PROVIDE
 PRODUCT APPROVAL FOR EACH.
 13-STORM SHUTTERS:
 A)PROVIDE KEY PLAN & COMPLETE INSTALLA-
 TION SCHEDULE. SEE CITY SAMPLE.
 B)CLEARLY MARK ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE &
 SPACING TO BE USED ACCORDING TO THE
 MEAN ROOF HEIGHT, DESIGN PRESSURES,
 EDGE DISTANCE, CONNECTION TYPE, PANEL
 SPAN AND STRUCTURE TO BE ATTACHED TO.
 **NOTE: WHEN INFORMATION IS NOT COMPLETE
 SUB-CONTRACTOR MAY APPLY FOR SEPARATE
 PERMIT. CITY IMPLEMENTATION STANDARD
 FOR HURRICANE MISSILE IMPACT PROTECT'N
 14-CONTRACTOR'S INSURANCE IS EXPIRED.
 15-SHEET A-1: REVISE GENERAL NOTE #1. WE
 USE FLORIDA BUILDING CODE 2001, NOT
 STANDARD BUILDING CODE.
 16-PAY IMPACT FEES TO PALM BEACH COUNTY
 AND BRING BACK STAMPED DRAWINGS AND
 PAID RECEIPT.
 17-NEED RECORDED NOTICE OF COMMENCEMENT.
 18-PROVIDE STRUCTURAL BUCK DETAILS FOR
 DOORS & WINDOWS. SEE SECTION 1707.4.4
 FBC 2001 FOR SPECIFIC REQUIREMENTS
 ACCORDINT TO BUCK SIZE.