Plan Review Notes
Plan Review Notes For Permit 03010597
Permit Number 03010597
Review Stop B
Sequence Number 2
Notes
Date Text
2003-03-06 00:00:001-DRAWINGS ARE STILL MISSING INFORMATION
 REQUIRED BY SEC. 1606.1.7 FBC 2001.
 SEE THIS SECTION FOR REQUIRED FIVE (5)
 ITEMS TO BE INCLUDED IN DRAWINGS.
 2-CLARIFY WHAT ARE THE DESIGN WIND
 PRESSURES WRITTEN BY HAND ON THE SITE
 PLAN. ARE THESE FOR COMPONENT AND
 CLADING?. AND, PLEASE DON'T WRITE INFO
 BY HAND. REVISE/UPDATE ORIGINAL DWGS.
 3-CLARIFY WHY WINDOWS ON BEDROOMS 1 & 2
 HAVE SAFETY GLASS?. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 4-DIMENSIONS GIVEN ON SITE PLAN DON'T
 ADD UP CORRECTLY. THEY EXCEED THE 50'
 OF LOT WIDTH. SEE DIMENSIONS GIVEN ON
 FRONT OF HOUSE AND REVISE AS REQUIRED.
 5-PROVIDE DETAIL/SPECIFICATIONS FOR
 CEILING INSTALLATION AT FRONT AND REAR
 PORCHES. CLEARLY SPECIFY ALL FASTENERS
 AND SPACING AS REQUIRED BY ASTM C926
 AND ASTM C1063. SEC. 2504.2 FBC 2001.
 6-STORM SHUTTERS INFORMATION SUBMITTED:
 A)DRAWINGS DON'T MATCH PRODUCT APPROVAL
 REPORT.
 B)ONLY ONE SET OF DRAWINGS SUBMITTED.
 PLEASE, PROVIDE 2 SETS WHEN RE-SUBMI-
 TTING CORRECT DRAWINGS.
  
 7-IMPACT FEES: NEED DRAWINGS STAMPED BY
 PALM BEACH COUNTY. SHOWING EITHER NO
 FEES DUE OR CREDIT FOR EXISTING HOUSE.
 8-ALL NEW DRAWINGS NEED TO BE RE-STAMPED
 BY HISTORIC PRIOR TO SUBMITTAL TO THIS
 OFFICE.
 9-NEED PRODUCT APPROVAL FOR ENTRY DOOR.
 SEE EXTERIOR ELEVATION FOR TYPE SHOWN.
 **NOTE: CLARIFY WHY ENTRY DOOR DOESN'T
 HAVE STORM SHUTTERS IF DOOR SHOWN ON
 EXTERIOR ELEVATION SHOWS GLASS IN IT.
 10-REVISE STRUCTURAL BUCK DETAIL. SEE
 SECTION 1707.4.4 FBC 2001 FOR SPECIFIC
 REQUIREMENTS FOR 2X BUCKS AND REVISE
 DETAIL ACCORDINGLY. ALSO, DRAW DETAIL
 AT A LARGER SCALE IN ORDER TO SEE IT.