2003-01-17 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THE FOLLOWING,MAKE
 CORRECTIONS,AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 ELECTRICAL CONTRACTOR TO PROVIDE SAME
 WHEN APPLYING FOR A PERMIT.
  
 2} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 3} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STAIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
  
 4} THE GROUNDING ELECTRODE SYSTEM MUST
 COMPLY WITH 250-50(A)(B)&(C),CWP IF
 AVAILABLE.
  
 5} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE PER 210-12.
  
 6} NOTE ALL KITCHEN COUNTERTOP
 RECEPTACLES SHALL BE GFCI'S PER
 210-8(A)(6).
  
 7} PROVIDE AN OUTLET FOR THE A/C
 EQUIPMENT PER210-63.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT, 8392