Date |
Text |
2003-01-17 00:00:00 | UNSAT |
| ~~~~~ |
| ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| PLEASE NOTE THE FOLLOWING,MAKE |
| CORRECTIONS,AND RESUBMIT FOR REVIEW. |
| |
| 1} PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW EQUIPMENT BEING INSTALLED. |
| MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| THE AVAILABLE FAULT CURRENT PER 110-9. |
| ELECTRICAL CONTRACTOR TO PROVIDE SAME |
| WHEN APPLYING FOR A PERMIT. |
| |
| 2} PLEASE LIST THE REQ`D BATH(S) |
| CIRCUIT(S). PER 210-11-C-3 |
| MUST BE 20A AND #12AWG. |
| |
| 3} SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| DWELLING UNIT. ROOMS WITH BATHS AND OR |
| CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| PER NFPA-72 2-2.1.1.1. |
| IN THE VICINITY OF BEDROOMS AND CLOSE |
| PROXIMITY OF STAIRWAYS. 2-5.2.1.3 |
| 3'FT FROM BATHS/KITCHENS.2-5.2.1.6 |
| |
| 4} THE GROUNDING ELECTRODE SYSTEM MUST |
| COMPLY WITH 250-50(A)(B)&(C),CWP IF |
| AVAILABLE. |
| |
| 5} PLEASE LIST THE REQ`D ARC |
| FAULT PROTECTED CIRCUITS ON PANEL |
| SCHEDULE PER 210-12. |
| |
| 6} NOTE ALL KITCHEN COUNTERTOP |
| RECEPTACLES SHALL BE GFCI'S PER |
| 210-8(A)(6). |
| |
| 7} PROVIDE AN OUTLET FOR THE A/C |
| EQUIPMENT PER210-63. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW |
| 561/659-8096 EXT, 8392 |