Plan Review Notes
Plan Review Notes For Permit 03010597
Permit Number 03010597
Review Stop B
Sequence Number 1
Notes
Date Text
2003-02-04 00:00:00BUILDING REVIEW CHECKLIST:
 1-SITE PLAN SHEET:
 A)PROVIDE SITE PLAN DRAWN TO SCALE.
 B)SPECIFY BUILDING SETBACKS.
 C)WHAT'S FSC SHOWN ON CODE EDITION USED.
 WE USE FLORIDA BUILDING CODE (FBC)2001
 D)BUILDING CODE/WIND LOAD DESIGN CERTI-
 FICATION IS MISSING SOME INFORMATION.
 SEE SEC. 1606.1.7 FBC 2001 FOR ALL
 FIVE ITEMS REQUIRED ON EVERY PROJECT.
  
 2-PROVIDE SURVEY WITH ORIGINAL SIGNATURE
 AND SEAL AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTES WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS.
 3-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE PLANS AND SEC. 2405.2 FBC 2001.
 4-SPECIFY SIZE OF ATTIC ACCESS. SECTION
 2309.6 FBC 2001.
 5-SPECIFY SIZE OF ATTIC VENTS. SECTION
 2309.7 FBC 2001.
 6-PROVIDE DETAILS/SPECIFICATIONS FOR
 CEILING INSTALLATION AT FRONT AND REAR
 PORCHES. AND, SPECIFY FASTENERS SIZE &
 SPACING AS REQUIRED BY ASTM C926 AND
 ASTM C1063. SEC. 2504.2 FBC 2001.
 7-CLARIFY WHAT IS SIMPSON LSTA24-4?.
 HOW IS THIS STRAP TIE USED TO CONNECT
 WOOD COLUMN TO THE BEAM. PROVIDE
 DETAIL FOR INTERMEDIATE AND CORNER
 COLUMNS SHOWING INSTALLATION. SEE
 SIMPSON CATALOGUE FOR INTENDED USE OF
 CONNECTOR. CLARIFY HOW ARE LATERAL
 LOADS TAKEN CARE OF. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 8-SHEET S-1:
 A)SPECIFY SUPPORTS AND SPACING FOR WWM
 IN CNCRETE SLAB. SEE SEC. 1909.3 FBC.
 B)SPECIFY SIZE OF VAPOR BARRIER. SEE
 SEC. 1909.2 FBC 2001.
 C)TYPICAL WALL SECTION: SPECIFY REQUIRED
 FIREBLOCKING. SEE SEC. 2305.1.4 FBC.
  
 9-FOOTING SIZE SPECIFIED ON FOUNDATION
 PLAN DOESN'T MATCH SIZE SHOWN ON WALL
 SECTION. REVISE AS REQUIRED.
 10-PROVIDE ROOF FRAMING PLAN SHOWING
 CALCULATED UPLIFT LOADS AND PROVIDE
 TRUSS ANCHOR SCHEDULE. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 11-A/C AREA AND UNDER ATTIC AREA SHOWN
 ON THE ENERGY CALCULATIONS DON'T MATCH
 PLANS. REVISE AS REQUIRED. ALSO, NEED
 SPECIFIC ADDRESS AS REQ'D BY CHAPTER
 13 FBC 2001.
 12-PROVIDE APPROVAL FOR EXTERIOR DOORS
 IS EXPIRED. ALSO, CLARIFY IF THIS IS
 THE SAME DOOR FOR ENTRY DOOR, REAR
 DOOR & STORAGE DOOR. OTHERWISE, NEED
 PRODUCT APPROVAL FOR EACH TYPE OF DOOR
 13-STORM SHUTTERS:
 A)PROVIDE KEY PLAN AND COMPLETE INSTA-
 LLATION SCHEDULE. SEE CITY SAMPLE.
 B)CLEARLY MARK ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE &
 SPACING TO BE USED ACCORDING TO THE
 MEAN ROOF HEIGHT, DESIGN PRESSURES,
 EDGE DISTANCE, CONNECTION TYPE, PANEL
 SPAN AND STRUCTURE TO BE ATTACHED TO.
 **NOTE: IF INFORMATION IS INCOMPLETE THE
 SUB-CONTRACTOR MAY APPLY FOR SEPARATE
 PERMIT. CITY IMPLEMENTATION STANDARD
 FOR HURRICANE MISSILE IMPACT PROTECT'N
 14-SHEET A-1: REVISE GENERAL NOTE #1.
 USE FLORIDA BUILDING CODE 2001, NOT
 STANDARD BUILDING CODE.
 15-PAY IMPACT FEES TO PALM BEACH COUNTY
 AND BRING BACK STAMPED DRAWINGS AND
 PAID RECEIPT.
 16-NEED RECORDED NOTICE OF COMMENCEMENT.
 17-PROVIDE STRUCTURAL BUCK DETAIL FOR
 DOORS & WINDOWS. SEE SECTION 1707.4.4
 FBC 2001 FOR SPECIFIC REQUIREMENTS
 ACCORDING TO BUCK SIZE.