2003-01-18 00:00:00DENIED;
 PAGE A-1 PLUMBING RISER DIAGRAM;
 1.ONLY FIXTURES IN THE BATHROOM GROUP
 SHALL CONNECT TO THE WET VENTED
 HORIZONTAL BRANCH DRAIN SEC. 909.1.
 2.SEE TABLE909.3 ONLY 4 FU'S PERMITED ON
 2" WET VENT.
 3.MASTER BATHROOM. FLOOR PLAN SHOWS 2
 LAVS. RISER DIAGRAM SHOWS 3.
 4.SINK ON 2ND FL. ON RISER DIAGRAM IS
 NOT SHOWN ON FLOOR PLAN.
 PLUMBING PLAN REVIEW BY;