Plan Review Notes For Permit 03010452 |
Permit Number |
03010452 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-01-18 00:00:00 | DENIED; | | PAGE A-1 PLUMBING RISER DIAGRAM; | | 1.ONLY FIXTURES IN THE BATHROOM GROUP | | SHALL CONNECT TO THE WET VENTED | | HORIZONTAL BRANCH DRAIN SEC. 909.1. | | 2.SEE TABLE909.3 ONLY 4 FU'S PERMITED ON | | 2" WET VENT. | | 3.MASTER BATHROOM. FLOOR PLAN SHOWS 2 | | LAVS. RISER DIAGRAM SHOWS 3. | | 4.SINK ON 2ND FL. ON RISER DIAGRAM IS | | NOT SHOWN ON FLOOR PLAN. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT.8369 |
|