2003-01-28 00:00:00*********** UNSAT ********************
  
 1)NOTE: PLEASE REMOVE SD FROM KITCHEN
 AREA. NOT PERMITTED PER NFPA-72 8-1.4.1.
 6.
  
 2)NOTE: PLEASE NOTE, MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN AND
 APNEL "B". SIZE PER 250-122
  
 3)NOTE: PLEASE SEE MIN SIZING OF GROUND-
 -ING ELECTRODE CONDUCTOR PER 250-66.
 PLEASE ALSO SEE MIN SIZE OF SERVICE
 CONDUCTORS FOR 400A SERVICE ON 310-15
 FOR SIZING GROUNDING ELECTRODE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  