Plan Review Notes
Plan Review Notes For Permit 03010450
Permit Number 03010450
Review Stop P
Sequence Number 2
Notes
Date Text
2003-03-01 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) COMMENTS FROM PREVIOUS REVIEW WERE
 NOT ADDRESSED.
 A) ONLY FIXTURES IN THE BATHROOM GROUP
 SHALL CONNECT TO THE WET VENTED HORI-
 ZONTAL BRANCH DRAIN. SEC 909.1. 2ND
 FLOOR LAUNDRY SHALL DRAIN DOWNSTREAM OF
 THE W/C AND SHOWER.
 B) MASTER BATH FLOOR PLAN SHOWS 2 LAVS,
 BUT RISER SHOWS 3? PLEASE CLAIRFY
 C) RISER DIAGRAM SHOWS SINK ON 2ND
 FLOOR, BUT NOT SHOWN ON FLOOR PLAN.
 PLEASE CLAIRFY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377