2003-03-10 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING CHANGES TO
 PLANS PRIOR TO ROUGH
 INSPECTION,RESUBMIT FOR REVIEW.
  
 1} THE LAUNDRY CIRCUIT ON THE PANEL
 SCHEDULE SHOULD BE CALCULATED @ 1500
 VA.PER210-16(B).
  
 2} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.ON PANEL
 SCHEDULE.
  
 3} THE GROUNDED ELECTRODE CONDUCTOR IS
 TOO SMALL FOR 400 AMP SERVICE,SEE
 250-66.SHOULD BE 1/0.
  
 4} THE FEEDER TO TO PANEL "B" SHOULD
 CONTAIN AN EQUIPMENT GROUND PER 250-122.
  
 5} THE SMOKE DETECTOR IN THE KITCHEN
 DOES NOT COMPLY WITH 8-1.4.2
 NFPA-72,SHOULD BE CHANGED TO A HEAT
 DETECTOR OR BE REMOVED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT 8392