Plan Review Notes For Permit 03010434 |
Permit Number |
03010434 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-01-16 00:00:00 | DENIED | | REFERENCE: FBC-2001 FUEL GAS | | | | 1) PLANS SHALL BE SIGNED AND SEALED BY | | THE ENGINEER OF RECORD. | | 2) ALL CUT SHEETS BTU RATINGS SHALL | | MATCH UP WITH BUT'S SHOWN ON GAS RISER. | | 3. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2001 | | FUEL GAS CODE. SHOW ALL MEASUREMENTS FOR | | DROPS AND LENGTH OF HEADER AT OVENS. | | 4. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE BEING USED. | | PE CHART SHOWN BUT NO PE PIPE SHOWN. | | 5. EMERGENCY HOOD SHUT DOWN SHUT OFF | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | DOWN STREAM OF MANUAL VALVE. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|