Plan Review Notes
Plan Review Notes For Permit 03010434
Permit Number 03010434
Review Stop P
Sequence Number 1
Notes
Date Text
2003-01-16 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1) PLANS SHALL BE SIGNED AND SEALED BY
 THE ENGINEER OF RECORD.
 2) ALL CUT SHEETS BTU RATINGS SHALL
 MATCH UP WITH BUT'S SHOWN ON GAS RISER.
 3. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. SHOW ALL MEASUREMENTS FOR
 DROPS AND LENGTH OF HEADER AT OVENS.
 4. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 PE CHART SHOWN BUT NO PE PIPE SHOWN.
 5. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377