Plan Review Notes For Permit 03010432 |
Permit Number |
03010432 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-02-10 00:00:00 | DENIED: | | REFERENCE PLAN SHEET A-9 & 10 NOTES: | | PLEASE CLARIFY HOW THE VENTILATION | | REQUIREMENTS ARE TO BE MET (.05 CFM PER | | SQ FT) WITHOUT INSTALLING THE CURBS & | | EXHAUST FANS. | | | | PROVISO: | | EXHAUST FANS FOR THE ELEC/PUMP ROOMS - | | EXHAUST SHALL NOT BE DIRECTED ONTO | | WALKWAYS AS PER 2001 FBC(M) 401.5.2. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|