Plan Review Notes
Plan Review Notes For Permit 03010432
Permit Number 03010432
Review Stop B
Sequence Number 1
Notes
Date Text
2003-02-11 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT SHALL BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 A COPY OF THE RECEIPT SUBMITTED, TO CITY
 OF WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) FBC 705.1.1.2NORTH END OF THE WEST
 ELEVATION.THAT SECTION OF THE WALL
 WHICH IS WITHIN 15 FEET OF THE PROPERTY
 LINE SHALL HAVE ALL OPENINGS EQUIPPED
 WITH APPROVED OPENING PROTECTIVES (SEE
 FBC 705.1.3) WITH A RATING OF NOT LESS
 THAN 3/4 HOUR.
  
 4) FBC* 1804.2.2SUBMIT A GEOTECHNICAL
 REPORT (REF: DRAWING SHEET S5.2,
 SITE WORK NOTE #2).
  
 5) FBC* 104.2.1.2FOUNDATION SECTION
 7/S4.1 (TYP).NO ANCHORAGE
 REINFORCEMENT IS SHOWN BETWEEN THE TILT-
 UP WALL PANELS AND THE FOUNDATIONS.
 SUBMIT AN ENGINEER'S SIGNED AND SEALED
 LETTER, CONFIRMING THAT NO ANCHORAGE TO
 THE FOUNDATION IS REQUIRED FOR UPLIFT OR
 FOR LATERAL LOAD DUE TO THE RETAINED
 FILL AND THE WAREHOUSE FLOOR SURCHARGE
 LOADS.
  
 6) NOTE:DETAIL 8/S4.1 HAS BEEN RED-
 LINED TO REFERENCE 9/S4.1 WHICH DOES NOT
 APPEAR TO BE CALLED UP ANYWHERE ON THE
 PLANS.
  
 7) PROVISO: FBC* 104.2.1.2 DETAIL 5/S4.4
 INCIDENTAL/MAINTENANCE LOADING ON THE
 CANTILEVER CONCRETE 'EYEBROW'.SUBMIT
 SHOP DRAWINGS OF THE MEANS OF ATTACHING
 THE 'EYEBROW' TO THE TILT-UP WALL PANEL.
  
 8) FBC* F102.2.4FIRE DISTRICT.AMEND
 THE PLANS TO INCLUDE THE REQUIREMENT FOR
 THE ROOF COVERING TO BE CLASS A OR B, AS
 THE BUILDING IS WITHIN THE FIRE DISTRICT
  
 9) SUBMIT A PRODUCT APPROVAL FOR THE
 PROPOSED ROOFING SYSTEM.
  
 10) SUBMIT A PRODUCT APPROVAL FOR THE
 PROPOSED HURRICANE MISSILE IMPACT
 PROTECTION SHUTTERS.
  
 11) METAL AWNINGS.SUBMIT DETAILS, OR
 A SEPARATE AWNING PERMIT APPLICATION
 WILL BE REQUIRED.
  
 12) A SEPARATE PERMIT APPLICATION WILL
 BE REQUIRED FOR THE DUMPSTER ENCLOSURE.
  
 13) NOTE:FBC 13-101.1.6ENERGY CODE
 COMPLIANCE SHALL BE DEMONSTRATED BY
 SUBMITTAL OF CODE COMPLIANCE FORM 400B
 WITH A LIST APPENDED TO DESCRIBE THE
 ASSUMPTIONS MADE ABOUT BUILDING FEATURES
 NOT INSTALLED DURING THIS PHASE OF THE
 PROJECT.
  
 14) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499