2004-02-19 00:00:00*********** UNSAT ******
  
 1)NOTE: PLEASE SEE PLANS ARE NOW SHOWING
 WHAT APPEARS TO BE A NEW SERVICE NOT ON
 ORIGINAL PLANS.
 PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2)NOTE: PLEASE SEE PLANS CONTAIN A TITLE
 BLOCK FOR THE ENGINEER. ORIGINAL PLANS
 WERE NOT SIGNED AND SEALED BY AN
 ENGINEER. TITLE BLOCK NEEDS TO BE
 REMOVED.
  
 3)NOTE: PLEASE VERIFY SERVICE ENT COND.,
 SHOWN W/ 2-3/0'S AND 1-#3??
  
 4)NOTE; PLEASE SEE NOTE 18, INDICATES
 ARC FAULT RECEPTS. ARC FAULT PROTECTION
 IS PROVIDED BY BRANCH BRKRS. 210.12
  
 5)NOTE: PLEASE SEE 225.31, DISC MEANS
 STILL REQ'D FOR "ARBOR" "GAZEBO" ON
 LOAD SIDE OF 3-WAY SWITCH.
  
 PLANS SENT TO BLDG REVIEW AS SIGNED
 AND SEALED BLDG PLANS WERE SUBMITTED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  