Notes
Date Text
2003-03-11 00:00:00************* REVISIONS/PROVISO*******
  
 1)NOTE: PLEASE PROVIDE LOAD CALCULATIONS
 THAT INCLUDE ALL EXSITING AND NEW. PER
 NEC 220
  
 2)NOTE: PLEASE SHOW MEANS OD DISC AT
 DETACHED STRUCTURE PER 225-31
 LTS AND GFI.
  
 3)NOTE: PLEASE REVISE ALL OTHER ITEMS
 NOTED ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ANY ELECTRICAL INSPECTION
 IS CALLED IN.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372