Plan Review Notes
Plan Review Notes For Permit 03010354
Permit Number 03010354
Review Stop E
Sequence Number 1
Notes
Date Text
2003-02-11 00:00:00*********** UNSAT **************
  
 1)NOTE: PLEASE SHOW SIZE OF EXSITING
 SERVICE AND LOAD ON EXSITING W/ NEW
 ADDED.
  
 2)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUIT FOR BEDRROM.210-12
  
 3)NOTE: PLEASE SHOW REQ`D DISC MEANS AT
 ARBOR PER 225-31
  
 4)NOTE: PLEASE MOVE SD TO BE SHOWN A MIN
 OF 5' FROM AHU. PER NFPA-72
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  