Plan Review Notes For Permit 03010354 |
Permit Number |
03010354 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-02-11 00:00:00 | *********** UNSAT ************** | | | | 1)NOTE: PLEASE SHOW SIZE OF EXSITING | | SERVICE AND LOAD ON EXSITING W/ NEW | | ADDED. | | | | 2)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | PROTECTED CIRCUIT FOR BEDRROM.210-12 | | | | 3)NOTE: PLEASE SHOW REQ`D DISC MEANS AT | | ARBOR PER 225-31 | | | | 4)NOTE: PLEASE MOVE SD TO BE SHOWN A MIN | | OF 5' FROM AHU. PER NFPA-72 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | 561-659-8096 EXT 8372 |
|