Plan Review Notes
Plan Review Notes For Permit 03010203
Permit Number 03010203
Review Stop B
Sequence Number 1
Notes
Date Text
2003-01-29 00:00:00BUILDING REVIEW CHECKLIST:
 1-AREA CALCULATIONS ARE WRONG. REVISE AS
 REQUIRED CALCULATIONS ON SHEET A-4.
 2-REVISE DESIGN PARAMETERS CRITERIA ON
 SHEET A1.1. MEAN ROOF HEIGHT IS 22'-0"
 +/- NOT 18"-6". SEE BUILDING HEIGHT ON
 CHAPTER 2 DEFINITIONS OF FBC 2001.
 3-DESIGN PARAMETERS CRITERIA ON SHEET
 A1.1 IS MISSING THE +/- INTERNAL
 PRESSURES AS REQUIRED BY SECTION
 1606.1.7 FBC 2001.
 4-REVISE SPECIFICATIONS FOR CEILING
 INSTALLATION AT FRONT & REAR PORCHES.
 SEE ASTM C-926 AND ASTM C-1063 FOR
 PROPER FASTENING TYPE, SIZE & SPACING.
 (SEC. 2504.2 FBC 2001).
 5-SPECIFY SPACING FOR WWM SUPPORTS IN
 CONCRETE SLAB AS REQUIRED BY SECTION
 1909.3 FBC 2001.
 6-LIBRARY ROOM. PROVIDE EGRESS WINDOWS
 THAT COMPLY WITH SEC. 1005.4.4 FBC/01
 OR CLEARLY SPECIFY UNDER ROOM NAME
 THAT SUCH ROOM IS NOT TO BE USED FOR
 SLEEPING PURPOSES (AS PER BUILDING
 OFFICIAL INTERPRETATION).
 7-GLASS BLOCK IN MASTER BATHROOM TO BE
 SAFETY GLASS IF FACE THICKNESS IS LESS
 THAN 0.25". SEC. 2405.2.2 FBC 2001.
 8-COMPLETE STRUCTURAL BUCK DETAIL FOR
 GARAGE DOOR. SPECIFY SIZE OF WASHER.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 9-REVISE 2X STRUCTURAL BUCK DETAIL FOR
 DOOR TO COMPLY WITH SEC. 1707.4.4.2
 FBC 2001.
 10-STORM SHUTTERS: A)SEE LIMITATIONS ON
 PAGE 8 OF 8 OF PRODUCT APPROVAL REPORT
 TO VERIFY IF STRUCTURE PROVIDES REQ'D
 STRENGTH.
 B)PROVIDE COMPLETE INSTALLATION SCHED.
 USING CITY SAMPLE ATTACHED.
 C)CLEARLY MARK ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE &
 SPACING TO BE USED ACCORDING TO THE
 MEAN ROOF HEIGHT, DESIGN PRESSURES,
 EDGE DISTANCE, PANEL SPAN, CONNECTION
 TYPE AND STRUCTURE TO BE ATTACHED TO.
  
 11-PROVIDE PRODUCT APPROVAL FOR:
 A)GLASS BLOCK WITH CLEAR DRAWINGS.
 B)WINDOW MULLIONS.
 C)FIXED WINDOW SIZE AS CALLED FOR LIVING
 D)GARAGE DOORS: CLEARLY MARK ON DRAWINGS
 MODEL TO BE USED AND CHECK THE DESIGN
 PRESSURES CALCULATED BY THE ARCHITECT.
  
 12-TYPICAL WALL SECTION ON SHEET AS1:
 REVISE ATTIC INSULATION VALUE. SEE THE
 ENERGY CALCULATIONS.