2003-01-29 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1-AREA CALCULATIONS ARE WRONG. REVISE AS |
| REQUIRED CALCULATIONS ON SHEET A-4. |
| 2-REVISE DESIGN PARAMETERS CRITERIA ON |
| SHEET A1.1. MEAN ROOF HEIGHT IS 22'-0" |
| +/- NOT 18"-6". SEE BUILDING HEIGHT ON |
| CHAPTER 2 DEFINITIONS OF FBC 2001. |
| 3-DESIGN PARAMETERS CRITERIA ON SHEET |
| A1.1 IS MISSING THE +/- INTERNAL |
| PRESSURES AS REQUIRED BY SECTION |
| 1606.1.7 FBC 2001. |
| 4-REVISE SPECIFICATIONS FOR CEILING |
| INSTALLATION AT FRONT & REAR PORCHES. |
| SEE ASTM C-926 AND ASTM C-1063 FOR |
| PROPER FASTENING TYPE, SIZE & SPACING. |
| (SEC. 2504.2 FBC 2001). |
| 5-SPECIFY SPACING FOR WWM SUPPORTS IN |
| CONCRETE SLAB AS REQUIRED BY SECTION |
| 1909.3 FBC 2001. |
| 6-LIBRARY ROOM. PROVIDE EGRESS WINDOWS |
| THAT COMPLY WITH SEC. 1005.4.4 FBC/01 |
| OR CLEARLY SPECIFY UNDER ROOM NAME |
| THAT SUCH ROOM IS NOT TO BE USED FOR |
| SLEEPING PURPOSES (AS PER BUILDING |
| OFFICIAL INTERPRETATION). |
| 7-GLASS BLOCK IN MASTER BATHROOM TO BE |
| SAFETY GLASS IF FACE THICKNESS IS LESS |
| THAN 0.25". SEC. 2405.2.2 FBC 2001. |
| 8-COMPLETE STRUCTURAL BUCK DETAIL FOR |
| GARAGE DOOR. SPECIFY SIZE OF WASHER. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 9-REVISE 2X STRUCTURAL BUCK DETAIL FOR |
| DOOR TO COMPLY WITH SEC. 1707.4.4.2 |
| FBC 2001. |
| 10-STORM SHUTTERS: A)SEE LIMITATIONS ON |
| PAGE 8 OF 8 OF PRODUCT APPROVAL REPORT |
| TO VERIFY IF STRUCTURE PROVIDES REQ'D |
| STRENGTH. |
| B)PROVIDE COMPLETE INSTALLATION SCHED. |
| USING CITY SAMPLE ATTACHED. |
| C)CLEARLY MARK ON DRAWINGS SPECIFIC |
| MOUNTING CONDITIONS AND ANCHOR TYPE & |
| SPACING TO BE USED ACCORDING TO THE |
| MEAN ROOF HEIGHT, DESIGN PRESSURES, |
| EDGE DISTANCE, PANEL SPAN, CONNECTION |
| TYPE AND STRUCTURE TO BE ATTACHED TO. |
| |
| 11-PROVIDE PRODUCT APPROVAL FOR: |
| A)GLASS BLOCK WITH CLEAR DRAWINGS. |
| B)WINDOW MULLIONS. |
| C)FIXED WINDOW SIZE AS CALLED FOR LIVING |
| D)GARAGE DOORS: CLEARLY MARK ON DRAWINGS |
| MODEL TO BE USED AND CHECK THE DESIGN |
| PRESSURES CALCULATED BY THE ARCHITECT. |
| |
| 12-TYPICAL WALL SECTION ON SHEET AS1: |
| REVISE ATTIC INSULATION VALUE. SEE THE |
| ENERGY CALCULATIONS. |