Plan Review Notes For Permit 02121183 |
Permit Number |
02121183 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-01-09 00:00:00 | ************** NOTES REDLINED******** | | | | 1)NOTE: PLEASE SEE KW FOR RANGE SHOWN | | PLANS(12KW) EXCEED 50A RATING OF BRKR. | | | | REVISE BEFORE ROUGH. | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|