2003-01-08 00:00:00 | ************ UNSAT ********************* | | | | 1)NOTE: PLEASE SEE MISSING RECEPT FOR | | KITCHEN COUNTERSPACE. 210-52C-1 | | | | 2)NOTE: PLEASE SEE LOAD CALCULATIONS, | | SHOWS 4SM APPL AND WASHER AT 1500W,,= | | 6KW, PLEASE ADJUST 5X1500 IS 7500W. | | | | 3)NOTE: PLEASE ALSONOTE ONLY TWO SM | | APPL ARE SHOWN ON PANEL SCHEDULE AND | | NOTE, 210-52/210-11C-1 | | | | 4)NOTE: PLEASE SEE LOAD CALCS, RANGE | | SHOWN AT 12KW W/ 50A OCP. PLEASE ADJUST | | OCP DUE TO LOAD BEING MORETHAN BRKR | | RATING. | | | | 5)NOTE: PLEASE SEE 2P-25A BRKR FOR AHU | | #2. PLEASE SIZE PER 424-3B FOR 10KW | | UNIT. | | | | 6)NOTE: PLEASE SEE, ALL DISC`S FOR AHU | | AND COND UNITS TO MEET 110-26 | | | | 7)NOTE: PLEASE SEE FS/FAC ALL PLANS MUST | | CONTAIN ORIGINAL DATE, SIGNATURE AND | | SEAL. 471.025 AND 481.221 FOR ARCH AND | | ENGINEERS. PLANS ARE NOW STAMPED?? | | THIS IS REQ`D FOR ALL SHEETS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|