2003-02-06 00:00:00 | SUBMITTAL CHECKLIST: |
| 1-PROVIDE COMPLETE WALL SECTION FROM |
| FOOTING TO CEILING FOR INTERIOR BEAR- |
| ING WALL AT GARAGE. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| 2-REVISE HANDRAIL HEIGHT SHOWN ON STAIR |
| SECTION. SEE SEC. 1007.5.1 FBC 2001. |
| **NOTE: HANDRAIL AND GUARDRAIL ARE NOT |
| THE SAME. |
| 3-SPECIFY SAFETY GLASS IN 2ND FLOOR |
| BATHROOM. SEC. 2405.2 FBC 2001. |
| 4-REVISE/CLARIFY DETAIL 4/S-2. HOW ARE |
| THE TWO TRUSSES RESTING ON TOP OF THIS |
| COLUMN. SEC. 104.2.1.2 CITY AMENDMENTS |
| TO FBC 2001. |
| **NOTE:SEE PLANS FOR ADDITIONAL COMMENTS |
| AND CLARIFY CONNECTORS AS REQUIRED. |
| SEE CONNECTORS LOCATION AND CLARIFY |
| HOW ARE SPECIFIED CONNECTORS INSTALLED |
| ON SUCH LOCATIONS. |
| 5-SPECIFY MISSING CONNECTORS. SEE |
| FRAMING PLANS FOR COMMENTS. |
| 6-BUILDING SECTION A-A CALLS FOR 6" |
| RECESS. FOOTING NEED TO BE 12" BELOW |
| GRADE. SEC. 1804.1.3 FBC 2001. CLARIFY |
| SEE SIZE OF FOOTER. |
| 7-VENT DRYER THRU ROOF, NOT WALL. THERE |
| ARE NOT OPENINGS ALLOWED IN ZERO LOT |
| LINE WALLS. TABLE 600 FBC 2001. |
| 8-SEE PLANS FOR COMMENTS AND RETURN |
| REVIEWED DRAWINGS AFTER CORRECTIONS |
| ARE DONE TO ORIGINAL CAD DRAWINGS TO |
| EXPEDITE THE REVIEW PROCESS. |