Plan Review Notes
Plan Review Notes For Permit 02121112
Permit Number 02121112
Review Stop R
Sequence Number 3
Notes
Date Text
2003-02-06 00:00:00SUBMITTAL CHECKLIST:
 1-PROVIDE COMPLETE WALL SECTION FROM
 FOOTING TO CEILING FOR INTERIOR BEAR-
 ING WALL AT GARAGE. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 2-REVISE HANDRAIL HEIGHT SHOWN ON STAIR
 SECTION. SEE SEC. 1007.5.1 FBC 2001.
 **NOTE: HANDRAIL AND GUARDRAIL ARE NOT
 THE SAME.
 3-SPECIFY SAFETY GLASS IN 2ND FLOOR
 BATHROOM. SEC. 2405.2 FBC 2001.
 4-REVISE/CLARIFY DETAIL 4/S-2. HOW ARE
 THE TWO TRUSSES RESTING ON TOP OF THIS
 COLUMN. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
 **NOTE:SEE PLANS FOR ADDITIONAL COMMENTS
 AND CLARIFY CONNECTORS AS REQUIRED.
 SEE CONNECTORS LOCATION AND CLARIFY
 HOW ARE SPECIFIED CONNECTORS INSTALLED
 ON SUCH LOCATIONS.
 5-SPECIFY MISSING CONNECTORS. SEE
 FRAMING PLANS FOR COMMENTS.
 6-BUILDING SECTION A-A CALLS FOR 6"
 RECESS. FOOTING NEED TO BE 12" BELOW
 GRADE. SEC. 1804.1.3 FBC 2001. CLARIFY
 SEE SIZE OF FOOTER.
 7-VENT DRYER THRU ROOF, NOT WALL. THERE
 ARE NOT OPENINGS ALLOWED IN ZERO LOT
 LINE WALLS. TABLE 600 FBC 2001.
 8-SEE PLANS FOR COMMENTS AND RETURN
 REVIEWED DRAWINGS AFTER CORRECTIONS
 ARE DONE TO ORIGINAL CAD DRAWINGS TO
 EXPEDITE THE REVIEW PROCESS.