2003-01-28 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| 1-PROVIDE COMPLETE SECTION/DETAIL AT |
| GARAGE INTERIOR BEARING WALL FROM |
| FOOTING TO 2ND FLOOR CEILING. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| 2-REVISE HANDRAIL HEIGHT SHOWN ON 2ND FL |
| PLAN AND STAIR SECTION. SEE SECTION |
| 1007.5.1 FBC 2001. |
| **NOTE: HANDRAIL AND GUARDRAIL ARE NOT |
| THE SAME. |
| 3-NEED SAFETY GLASS IN 2ND FL BATHROOM. |
| SEC. 2405.2 FBC 2001. |
| 4-REVISE/CLARIFY DETAIL 4/S-2. FRAMING |
| PLAN SHOW COLUMN RECEIVING TWO GIRDER |
| TRUSSES, NOT JUST ONE. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| 5-REVISE ROOF DIAPHRAGM FOR SHEATHING |
| FASTENING ZONES ON SHEET S-3. MISSING |
| SOME ZONE 3 AREAS AT THE CORNERS. SEE |
| PLANS AND SEC. 2306.1 CITY AMENDMENTS |
| 6-2ND FLOOR AND ROOF FRAMING PLANS ARE |
| MISSING SOME CONNECTORS. SEE PLANS. |
| 7-STORM SHUTTERS: NEED COMPLETE PRODUCT |
| APPROVAL AND MARK ON APPROVED DRAWINGS |
| SPECIFIC MOUNTING CONDITIONS & ANCHOR |
| TYPE AND SPACING TO BE USED. |
| 8-REVISE DETAIL FOR 2X STRUCTURAL BUCK |
| DETAIL FOR DOOR. SEE SEC. 1707.4.4.2 |
| FBC 2001. |
| 9-PROVIDE COMPLETE STRUCTURAL DETAIL FOR |
| WATER HEATER PROTECTION BOLLARD. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| 10-BUILDING SECTION A-A ON SHEET A-4 |
| CALLS FOR 6" RECESS. CLARIFY HOW IS |
| FOOTING TO BE 12" BELOW GRADE AS REQ'D |
| BY SEC. 1804.1.3 FBC 2001 IF FOOTING |
| IS ONLY 16" DEEP. |
| 11-COMPLETE SPECIFICATIONS FOR GARAGE |
| DOOR STRUCTURAL BUCK. SPECIFY WASHER. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 12-USP TA20 STRAP SPECIFIED FOR (3)2X4 |
| COLUMN IS FOR CONCRETE APPLICATION. |
| SPECIFY WOOD CONNECTOR AS REQUIRED. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 13-SHEET A-5: UPDATE CONNECTOR SPECIFIED |
| ON FRAME TO CONC. BLOCK WALL DETAIL. |
| SEMCO IS OUT OF BUSINESS. |
| 14-VENT DRYER TO ROOF. THERE ARE NOT |
| OPENINGS ALLOWED ON WALL AT ZERO LOT |
| LINE. TABLE 600 FBC 2001. |