Plan Review Notes
Plan Review Notes For Permit 02121112
Permit Number 02121112
Review Stop R
Sequence Number 1
Notes
Date Text
2003-01-28 00:00:00BUILDING REVIEW CHECKLIST:
 1-PROVIDE IMPACT FEES PAID RECEIPT.
 2-PROVIDE NOTICE OF COMMENCEMENT.
 3-PROVIDE COMPLETE SECTION/DETAIL AT
 GARAGE INTERIOR BEARING WALL FROM
 FOOTING TO 2ND FLOOR CEILING. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 4-PROVIDE SOIL TEST REPORT.
 5-REVISE HANDRAIL HEIGHT SHOWN ON 2ND FL
 PLAN AND STAIR SECTION. SEE SECTION
 1007.5.1 FBC 2001.
 **NOTE: HANDRAIL AND GUARDRAIL ARE NOT
 THE SAME.
 6-NEED SAFETY GLASS IN 2ND FL. BATHROOM.
 SEE PLANS AND SEC. 2405.2 FBC 2001.
 7-VERIFY THAT EGRESS WINDOWS SH24+5 AND
 SH34+5 PROVIDE 24" MIN. CLEAR HEIGHT &
 5.7S.F. MIN. CLEAR OPENING AS REQUIRED
 BY SEC. 1005.4.4 FBC 2001.
 8-REVISE/CLARIFY DETAIL 4/S-2. FRAMING
 PLAN SHOW COLUMN RECEIVING 2 GIRDER
 TRUSSES, NOT JUST ONE. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 9-REVISE ROOF DIAPHRAGM FOR SHEATHING
 FASTENING ZONES ON SHEET S-3.MISSING
 SOME ZONE 3 AREAS. SEE PLANS AND SEC.
 2306.1 CITY AMENDMENTS TO FBC 2001.
 10-ROOF FRAMING PLAN IS MISSING SOME
 CONNECTORS. SPECIFY AS REQUIRED. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 11-PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS OR APPLY FOR SEPARATE
 PERMIT. SEE CITY IMPLEMENTATION
 STANDARD FOR MISSILE IMPACT PROTECTION
 12-PROVIDE PRODUCT APPROVAL FOR:
 A)ROOF TILE. (ONE SUBMITTED IS EXPIRED).
 B)ENTRY DOORS. NEED FIRST PAGE OF REPORT
 TO HAVE THE DADE COUNTY LOGO AT THE
 BOTTOM LEFT AND APPROVED DRAWINGS WITH
 DADE COUNTY APPROVAL STAMP MATCHING
 RENEWED PRODUCT APPROVAL NUMBER.
 13-REVISE ENERGY CALCULATIONS AS FOLLOWS
 A)PROVIDE COMPLETE/CORRECT ADDRESS.
 B)PROVIDE CORRECT OWNER'S INFORMATION.
 C)PROVIDE CORRECT BUILDER'S INFORMATION.
 D)COMPLETE INFORMATION ON TOP OF FORM.
 E)OWNER/AGENT TO SIGN AND DATE BOTTOM OF
 FORM ALSO.
 14-REVISE DETAIL FOR 2X STRUCTURAL BUCK
 DETAIL FOR DOOR. SEE SEC. 1707.4.4.2
 FBC 2001.
 15-PROVIDE COMPLETE STRUCTURAL DETAIL
 FOR WATER HEATER PROTECTION BOLLARD.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 16-BUILDING SECTION A-A ON SHEET A-4
 CALLS FOR 6" RECESS. CLARIFY HOW IS
 THE FOOTING GOING TO BE 12" BELOW
 GRADE AS REQUIRED BY SEC. 1804.1.3 FBC
 IF FOOTING IS ONLY 16" HIGH?
 17-COMPLETE SPECIFICATIONS FOR GARAGE
 DOOR STRUCTURAL BUCK. SPECIFY WASHERS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 18-USP TA20 STRAP SPECIFIED FOR (3)2X4
 COLUMN IS FOR CONCRETE APPLICATION.
 PROVIDE WOOD CONNECTOR AS REQUIRED.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.