2003-01-28 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1-PROVIDE IMPACT FEES PAID RECEIPT. |
| 2-PROVIDE NOTICE OF COMMENCEMENT. |
| 3-PROVIDE COMPLETE SECTION/DETAIL AT |
| GARAGE INTERIOR BEARING WALL FROM |
| FOOTING TO 2ND FLOOR CEILING. SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| 4-PROVIDE SOIL TEST REPORT. |
| 5-REVISE HANDRAIL HEIGHT SHOWN ON 2ND FL |
| PLAN AND STAIR SECTION. SEE SECTION |
| 1007.5.1 FBC 2001. |
| **NOTE: HANDRAIL AND GUARDRAIL ARE NOT |
| THE SAME. |
| 6-NEED SAFETY GLASS IN 2ND FL. BATHROOM. |
| SEE PLANS AND SEC. 2405.2 FBC 2001. |
| 7-VERIFY THAT EGRESS WINDOWS SH24+5 AND |
| SH34+5 PROVIDE 24" MIN. CLEAR HEIGHT & |
| 5.7S.F. MIN. CLEAR OPENING AS REQUIRED |
| BY SEC. 1005.4.4 FBC 2001. |
| 8-REVISE/CLARIFY DETAIL 4/S-2. FRAMING |
| PLAN SHOW COLUMN RECEIVING 2 GIRDER |
| TRUSSES, NOT JUST ONE. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| 9-REVISE ROOF DIAPHRAGM FOR SHEATHING |
| FASTENING ZONES ON SHEET S-3.MISSING |
| SOME ZONE 3 AREAS. SEE PLANS AND SEC. |
| 2306.1 CITY AMENDMENTS TO FBC 2001. |
| 10-ROOF FRAMING PLAN IS MISSING SOME |
| CONNECTORS. SPECIFY AS REQUIRED. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| 11-PROVIDE COMPLETE INFORMATION FOR |
| STORM SHUTTERS OR APPLY FOR SEPARATE |
| PERMIT. SEE CITY IMPLEMENTATION |
| STANDARD FOR MISSILE IMPACT PROTECTION |
| 12-PROVIDE PRODUCT APPROVAL FOR: |
| A)ROOF TILE. (ONE SUBMITTED IS EXPIRED). |
| B)ENTRY DOORS. NEED FIRST PAGE OF REPORT |
| TO HAVE THE DADE COUNTY LOGO AT THE |
| BOTTOM LEFT AND APPROVED DRAWINGS WITH |
| DADE COUNTY APPROVAL STAMP MATCHING |
| RENEWED PRODUCT APPROVAL NUMBER. |
| 13-REVISE ENERGY CALCULATIONS AS FOLLOWS |
| A)PROVIDE COMPLETE/CORRECT ADDRESS. |
| B)PROVIDE CORRECT OWNER'S INFORMATION. |
| C)PROVIDE CORRECT BUILDER'S INFORMATION. |
| D)COMPLETE INFORMATION ON TOP OF FORM. |
| E)OWNER/AGENT TO SIGN AND DATE BOTTOM OF |
| FORM ALSO. |
| 14-REVISE DETAIL FOR 2X STRUCTURAL BUCK |
| DETAIL FOR DOOR. SEE SEC. 1707.4.4.2 |
| FBC 2001. |
| 15-PROVIDE COMPLETE STRUCTURAL DETAIL |
| FOR WATER HEATER PROTECTION BOLLARD. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 16-BUILDING SECTION A-A ON SHEET A-4 |
| CALLS FOR 6" RECESS. CLARIFY HOW IS |
| THE FOOTING GOING TO BE 12" BELOW |
| GRADE AS REQUIRED BY SEC. 1804.1.3 FBC |
| IF FOOTING IS ONLY 16" HIGH? |
| 17-COMPLETE SPECIFICATIONS FOR GARAGE |
| DOOR STRUCTURAL BUCK. SPECIFY WASHERS. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 18-USP TA20 STRAP SPECIFIED FOR (3)2X4 |
| COLUMN IS FOR CONCRETE APPLICATION. |
| PROVIDE WOOD CONNECTOR AS REQUIRED. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |