Plan Review Notes For Permit 02121111 |
Permit Number |
02121111 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-01-08 00:00:00 | *************** UNSAT ***************** | | | | 1)NOTE: PLEASE SEE MISSING RECEPT FOR | | KITCHEN COUNTERSPACE AS PER 210-52C-1 | | | | 2)NOTE: PLEASE SEE LOAD CALCULATIONS, | | SHOWS 4 SM APPL AND WASHER AT 6KW, ?? | | PLEASE SEE 5 AT 1500 KW MIN IS 7500W? | | PLEASE ADJUST. | | | | 3)NOTE: PLEASE NOTE ONLY TWO SMALL APPL | | IS SHOWN ON PANEL SCHEDULE AND THOSE | | ARE THE SHARED W/ DIN/NOOK. PLEASE NOTE | | OTHER TWO MUST ONLY BE FOR KITCHEN | | 210-11C-1 | | | | 4)NOTE: PLEASE SEE LOAD CALCS, RANGE | | SHOWN AT 12KW AND PANEL SCHEDULE SHOWS | | ONLY 2P50A OCP. PLEASE ADJUST OCP TO | | MEET LOAD. | | | | 5)NOTE: PLEASE SEE 2P-25A OCP FOR AHU #2 | | PLEASE SEE 424-3B 10KW? 60A OCP. PLEASE | | ADJUST. | | | | 6)NOTE: PLEASE NOTE, ALL DISC`S FOR A/C | | UNITS TO MEET 110-26. | | | | 7)NOTE: PLEASE NOTE, ALL PLANS MUST | | CONTAIN ORIGINAL SIGNATURE, DATE, SEAL | | PER FS/FAC. 471.025 AND 481.221 FOR ARCH | | AND ENGINEERS. THIS IS FOR ALL SHEETS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|