Plan Review Notes For Permit 02121110 |
Permit Number |
02121110 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-01-08 00:00:00 | **************** UNSAT *************** | | | | 1)NOTE: PLEASE SEE MISSING RECEPT FOR | | KITCHEN COUNTERSPACE.210-52C1 | | | | 2)NOTE: PLEASE SEE LOAD CALCULATIONS, | | PLEASE SEE 4-SM APPL AND WASHER AT 1500W | | SHOWN AT 6KW,, PLEASE SEE 5@1500W = 7500 | | | | 3)NOTE: PLEASE ALSO NOTE ONLY TWO SMALL | | APPL CIRCUITS SHOWN ON PANEL SCHEDULE? | | 210-52/210-11C-1 | | | | 4)NOTE: PLEASE SEE LOAD CALCS, RANGE | | SHOWN AT 12KW W/ 2P50A OCP. PLEASE | | ADJUST OCP TO MEET LOAD OF RANGE. | | 12KW EXCEEDS RATING OF 50A BRKR. | | | | 5)NOTE: PLEASE SEE 2P-25A BRKR ON 10KW | | HEAT/AHU #2. PLEASE SEE 424-3B FOR | | SIZING OF OCP. MIN 125%. | | AHU#1 SHOWN W/ 60A OCP FOR SAME SIZE | | UNIT. | | | | 6)NOTE: PLEASE SEE PLANS, ALL DISC`S TO | | MEET 110-26. PLEASE NOTE. | | | | 7)NOTE: PLEASE SEE FS/FAC FOR ALL PLANS | | REQ`D TO HAVE ORIGINAL SIGNATURE, DATE | | AND SEAL. 471.025 AND 481.22 FOR ARCH | | AND ENGINEERS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|