Plan Review Notes For Permit 02121047 |
Permit Number |
02121047 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-12-27 00:00:00 | ************* UNSAT *************** | | | | 1)NOTE: PLEASE NOTE, DUE TO PANEL BEING | | LOCATED IN SPACE NEXTDOOR. PLEASE | | PROVIDE ACCESS TO ELECTRICAL ROOM FROM | | ONE SPACE TO ANOTHER. PLEASE NOTE, EVEN | | IF SAME TENANT USES BOTH SPACES, THAT | | MAY CHANGE OR TENANT MAY MOVE OUT. ONE | | TENANT MUST HAVE ACCESS TO THEIR BRKRS | | FOR TURNING ON OR OFF POWER. IF ONE | | TENANT IS AWAY, THE OTHER MAY BE "LOCKED | | OUT". PLEASE ALSO SEE FIRE COMMENTS FOR | | ANY CONDITIONS THEY MAY HAVE WITH DOOR | | ACCESS/ AND/OR EXITING. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|