Plan Review Notes
Plan Review Notes For Permit 02120892
Permit Number 02120892
Review Stop P
Sequence Number 2
Notes
Date Text
2003-03-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT 2 - MAXIMUM SQUARE FOOTAGE TO BE
 DRAINED ON 4" PIPE @ 2% IS 2355. BELOW
 ROOF AREA SHOWS 2434 SQUARE FEET BEING
 DRAINED ON HORIZONTAL PIPE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377