Plan Review Notes
Plan Review Notes For Permit 02120892
Permit Number 02120892
Review Stop P
Sequence Number 1
Notes
Date Text
2003-01-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED FOR EACH WAREHOUSE BAY. ALSO
 SEE SECTION 410.1
 2) SHT 7 PLEASE PROVIDE CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106 AND 1107. ADD 1/2 AREA OF
 ALL VERTICAL WALLS. MAXIMUM OF 1600 SQ
 FT FOR HORIZONTAL 4" PIPE. SHOW TOTAL
 SQUARE FOOTAGE FOR ROOF AND TOTAL DRAIN-
 ING INTO EACH DRAIN.
 3) PLEASE PROVIDE A STORM RISER DIAGRAM.
 INDICATE PIPE SIZE AND SHOW ACCUMULATED
 SQ FT AT EACH RISER.
 4) SHT 13 THERMAL EXPANSION CONTROL IS
 REQUIRED. SECTION 607.3.2 PLEASE SHOW AN
 EXPANSION TANK AT WATER HEATER DETAIL.
 5) RPZ BACKFLOW REQUIRED ON WATER SERV-
 ICE.
 6) SHT 13 GENERAL MECHANICAL NOTE #10,
 AIR CHAMBERS ARE NOT APPROVED. PLEASE
 PROVIDE WATER HAMMER ARRESTORS REQUIRED
 IN SECTION 604.9
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377