Plan Review Notes For Permit 02120892 |
Permit Number |
02120892 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-01-11 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 11 | | | | 1) PER TABLE 403.1 A DRINKING FOUNTAIN | | IS REQUIRED FOR EACH WAREHOUSE BAY. ALSO | | SEE SECTION 410.1 | | 2) SHT 7 PLEASE PROVIDE CALCULATIONS FOR | | PRIMARY AND SECONDARY ROOF DRAINS PER | | SECTIONS 1106 AND 1107. ADD 1/2 AREA OF | | ALL VERTICAL WALLS. MAXIMUM OF 1600 SQ | | FT FOR HORIZONTAL 4" PIPE. SHOW TOTAL | | SQUARE FOOTAGE FOR ROOF AND TOTAL DRAIN- | | ING INTO EACH DRAIN. | | 3) PLEASE PROVIDE A STORM RISER DIAGRAM. | | INDICATE PIPE SIZE AND SHOW ACCUMULATED | | SQ FT AT EACH RISER. | | 4) SHT 13 THERMAL EXPANSION CONTROL IS | | REQUIRED. SECTION 607.3.2 PLEASE SHOW AN | | EXPANSION TANK AT WATER HEATER DETAIL. | | 5) RPZ BACKFLOW REQUIRED ON WATER SERV- | | ICE. | | 6) SHT 13 GENERAL MECHANICAL NOTE #10, | | AIR CHAMBERS ARE NOT APPROVED. PLEASE | | PROVIDE WATER HAMMER ARRESTORS REQUIRED | | IN SECTION 604.9 | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|