Plan Review Notes For Permit 02120892 |
Permit Number |
02120892 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-01-17 00:00:00 | DENIED: | | | | 1.PROVIDE OUTSIDE AIR CALCULATIONS AS | | PER 2001 FBC(M) TABLE 403.3 OR ASHRAE | | 62-89.PROVIDE CALCS FOR ALL AREAS OF | | THE BUILDING. | | | | 2.PROVIDE SUBMITTAL FOR THE FIRE | | DAMPERS SHOWN ON PLAN SHEET 13, ACCESS | | DOORS REQUIRED. | | | | 3.AS PER 2001 FBC(M) 606.2.2, DUCT | | SMOKE DETECTORS REQUIRED.FAN SHUTDOWN | | BY DUCT SMOKE DETECTOR SHALL HAVE | | NOTIFICATION TO ALARM/STROBE IN NORMALLY | | OCCUPIED AREAS NFPA 90A 4-4.4.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|