Plan Review Notes
Plan Review Notes For Permit 02120892
Permit Number 02120892
Review Stop M
Sequence Number 1
Notes
Date Text
2003-01-17 00:00:00DENIED:
  
 1.PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER 2001 FBC(M) TABLE 403.3 OR ASHRAE
 62-89.PROVIDE CALCS FOR ALL AREAS OF
 THE BUILDING.
  
 2.PROVIDE SUBMITTAL FOR THE FIRE
 DAMPERS SHOWN ON PLAN SHEET 13, ACCESS
 DOORS REQUIRED.
  
 3.AS PER 2001 FBC(M) 606.2.2, DUCT
 SMOKE DETECTORS REQUIRED.FAN SHUTDOWN
 BY DUCT SMOKE DETECTOR SHALL HAVE
 NOTIFICATION TO ALARM/STROBE IN NORMALLY
 OCCUPIED AREAS NFPA 90A 4-4.4.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.