Plan Review Notes
Plan Review Notes For Permit 02120892
Permit Number 02120892
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-01-03 00:00:001) PLEASE INDICATE LOCATIONS OF ANY
 EXISTING FIRE HYDRANTS IN THE VICINITY
 OF THE BUILDING.
  
 2) HOW IS FIRE AND PARAMEDICAL EQUIPMENT
 EXPECTED TO USE THE NEW GATES. ARE THE
 NEW GATES ELECTRIC OR MANUAL.
  
 3) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION.
  
 4) PLEASE INDICATE LOCATIONS OF
 EMERGENCY LIGHTING EQUIPMENT WITHIN
 TENANT SPACE.
  
 5) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 6) WHAT IS THE SEPARATION BETWEEN THE
 WAREHOUSE AND OFFICE AREA.
  
 7) PLEASE EXPLAIN SINGLE EXIT THEORY
 FROM SECOND LEVEL STORAGE AREA.
  
 8) WHAT WILL THE PRINCIPAL USE OF THE
 SEVEN RENTAL UNITS.
  
 9) PLEASE INDICATE CONSTRUCTION TYPE
 FOR THE BUILDING.
  
 10) PLEASE EXPLAIN HOW THE GLASS
 SPECIALITIES AREA BE USED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910