Plan Review Notes
Plan Review Notes For Permit 02120892
Permit Number 02120892
Review Stop E
Sequence Number 1
Notes
Date Text
2003-01-13 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE, PER FS/FAC 61G15-23
 .002. PLANS THAT ARE SIGNED AND SEALED
 BY AN ENGINEER MUST HAVE A TITLE BLOCK
 CONTAINING ALL INFORMATION AS SET FORTH
 IN FS.
  
 2)NOTE: PLEASE SEE FIRE REVIEW NOTES FOR
 EMERGENCY LIGHTING. PLEASE ALSO SEE
 700-12E FOR CIRCUTING OF EXT AND EM LTS.
  
 3)NOTE: PLEASE SEE 600-5 FOR REQ`D SIGN
 CIRCUIT.
  
 4)NOTE: PLEASE CLARFIY EGRESS LIGHTING
 FOR STAIRWAY.
  
 5)NOTE: PLEASE CLARIFY VOLTAGE, PANELS
 SHOW 120/208V AND YET RISER SHOWS A
 HIGH LEG? Y OR DELTA SYSTEM?
  
 6)NOTE: PLEASE CLARIFY EQUIPMENT GROUND-
 ING METHOD BETWEEN MAIN DISC/GUTTER AND
 PANELS P/T. SIZE PER 250-122
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372