Plan Review Notes For Permit 02120892 |
Permit Number |
02120892 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-01-13 00:00:00 | ************** UNSAT **************** | | | | 1)NOTE: PLEASE NOTE, PER FS/FAC 61G15-23 | | .002. PLANS THAT ARE SIGNED AND SEALED | | BY AN ENGINEER MUST HAVE A TITLE BLOCK | | CONTAINING ALL INFORMATION AS SET FORTH | | IN FS. | | | | 2)NOTE: PLEASE SEE FIRE REVIEW NOTES FOR | | EMERGENCY LIGHTING. PLEASE ALSO SEE | | 700-12E FOR CIRCUTING OF EXT AND EM LTS. | | | | 3)NOTE: PLEASE SEE 600-5 FOR REQ`D SIGN | | CIRCUIT. | | | | 4)NOTE: PLEASE CLARFIY EGRESS LIGHTING | | FOR STAIRWAY. | | | | 5)NOTE: PLEASE CLARIFY VOLTAGE, PANELS | | SHOW 120/208V AND YET RISER SHOWS A | | HIGH LEG? Y OR DELTA SYSTEM? | | | | 6)NOTE: PLEASE CLARIFY EQUIPMENT GROUND- | | ING METHOD BETWEEN MAIN DISC/GUTTER AND | | PANELS P/T. SIZE PER 250-122 | | | | PLEASE SUBMIT THE ABOVE INFORMAITON FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|