2003-01-23 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 659 8096 EXT 8499 |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| 1) FBC* 104.2.4SITE SURVEY.A SIGNED |
| AND SEALED SURVEY DRAWING PREPARED BY A |
| QUALIFIED SURVEYOR IS REQUIRED (REF: |
| 472.025(1) FL. STATUTES.) |
| |
| 2) FBC* 104.1.1DUMPSTER.A SEPARATE |
| PERMIT APPLICATION WILL BE REQUIRED FOR |
| THE DETACHED DUMPSTER ENCLOSURE. |
| |
| 3) FBC* 104.1.1AWNINGS.A SEPARATE |
| PERMIT APPLICATION WILL BE REQUIRED FOR |
| THE INSTALLATION OF THE VINYL AWNINGS. |
| |
| 4) FBC T500 AND T600THE PLANS SHALL |
| STATE WHETHER THE BUILDING IS |
| SPRINKLERED OR UNSPRINKLERED. |
| |
| 5) FBC 704.3TENANT SEPARATION WALLS. |
| THE PLANS SHALL BE AMENDED TO STATE THE |
| 1-HOUR FIRE RATING REQUIREMENT FOR THE |
| TENANT FIRE SEPARATION WALLS AT THE |
| TOILETS AND 'FUTURE PARTITION' LOCATIONS |
| |
| 6) FBC 1027.1.1NUMBER OF EXITS FROM |
| THE STORAGE LOFT.THE 'LOFT' DOES NOT |
| MEET THE FBC 503.2.3.2 REQUIREMENTS FOR |
| A MEZZANINE, AND SO MUST BE CONSIDERED |
| AS A SECOND STORY.A SINGLE EXIT IS |
| ONLY PERMITTED IN A STORAGE OCCUPANCY |
| WITH A MAXIMUM OF ONE STORY.A SECOND |
| MEANS OF EGRESS IS REQUIRED FROM THE |
| STORAGE LOFT. |
| |
| 7) SHEET 8, SECTION 1.STORAGE LOFT |
| FLOOR.THE STATED LISTING NUMBER |
| 'UL 501' DOES NOT APPEAR TO BE A VALID |
| LISTING.SHOULD THIS BE 'UL# L501'? |
| AMEND THE PLANS AS NECESSARY. |
| |
| 8) SUBMIT A PRODUCT APPROVAL FOR THE |
| PROPOSED ROOFING. |
| |
| 9) ROLL-UP DOOR PRODUCT APPROVAL.THE |
| DOOR ELEVATIONS ON PLAN SHEET #2, |
| SPECIFY A 16'-0" WIDE DOOR.THIS WIDTH |
| APPEARS TO BE OUTSIDE THE SCOPE OF THE |
| SUBMITTED ROLL-UP DOOR PRODUCT APPROVAL |
| NOA# 00-0508.1.THE PRODUCT APPROVAL |
| DRAWING SHEETS ARE NOT COMPLETELY |
| LEGIBLE BUT THE PLAN VIEW ON SHEET 1 |
| SHOWS A MAXIMUM DOOR WIDTH WHICH IS LESS |
| THAN 16'-0".SUBMIT AN APPROPRIATE |
| PRODUCT APPROVAL OR REVISE THE PLANS |
| ACCORDINGLY. |
| |
| 10) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| OLD SHEETS SHALL BE REMOVED AND THE NEW |
| SHEETS INSERTED.ONE COPY OF EACH OLD |
| SHEET SHALL BE INCLUDED WITH THE |
| RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |