Plan Review Notes
Plan Review Notes For Permit 02120827
Permit Number 02120827
Review Stop P
Sequence Number 1
Notes
Date Text
2002-12-21 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) COMPLY WITH FBC-2001 SEC 424.2
 PRIVATE SWIMMING POOLS. (ADD TO NOTES)
 2) FBC-2001424.2.6.6.3 (1,2,3) ENTRAP-
 MENT AVOIDANCE. (DETAIL) THIS DETAIL NOT
 CLEAR (SECTION 104.2.1 FBC CHAPTER 1)
 3) FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER. (DETAIL) THIS DETAIL IS NOT
 CLEAR (SECTION 104.2.1 FBC CHAPTER 1)
 4) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 5) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 19) FBC-2001 104.2 BUILDING DRAWINGS, &
 SPECIFICATIONS. TOO MANY SWIMMING POOL
 PIPING SCHEMATICS ON THE PLANS. THIS IS
 VERY CONFUSING. SHOW INDIVIDUAL PIPING
 SCHEMATIC FOR POOL BEING BUILT,W/SPA.
 SHOW PIPING FOR THE ENTIRE SYSTEM, PIPE
 SIZES, VENTS, SUCTION AND DISCHARGE PIP-
 ING EXT. DELETE ALL OTHER SCHEMATICS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377