Plan Review Notes
Plan Review Notes For Permit 02120762
Permit Number 02120762
Review Stop E
Sequence Number 3
Notes
Date Text
2003-02-21 00:00:00************** NOTES REDLINED *******
  
 PLEASE VERIFY AND SIZE ALL OCP AND
 WIRE SIZES FOR A/C UNITS PER MANUFACT.
 NAMEPLATE AND NEC. PANEL SCHEDULE SHOWS
 100A OCP ON #6,,,ETC.
  
  
 PLEASE REVISE BEFORE FINAL AND SUBMIT
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372