Plan Review Notes For Permit 02120762 |
Permit Number |
02120762 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-02-08 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 11 | | | | 1) RESPONSE NOTED FOR SEPARATE FACILIT- | | IES, BUT DATA ON SHT A-1 STILL CALLS FOR | | EXCEPTION #4. PLEASE CHANGE DATA TO CALL | | OUT FOR EXCEPTION #2 AND INDICATE NUMBER | | OF PEOPLE THAT WILL BE EMPLOYED AS IN- | | DICATED IN SECTION 403.2 | | 2) RESPONSE NOTED FOR BOTTLED WATER. | | PLEASE SHOW ON PLANS. WATER COOLER SHALL | | BE ARI-1010 COMPLIANT PER 410.1. MANUF. | | INFORMATION REQUIRED. | | 3) SHT P-1 VACUUM RELIEF VALVE IS NOT | | FOR THERMAL EXPANSION CONTROL. AN EXPAN- | | SION TANK IS REQUIRED AT WATER HEATER. | | 4) SHT A-2 SHOWER DOES NOT COMPLY WITH | | 11-4.21.2 ( SHOWER STALL SIZE AND CLEAR | | FLOOR SPACE SHALL COMPLY WITH FIG. 35(A) | | OR (B). NO DETAILS FOR SEAT HEIGHT 11-4. | | 21.3, GRAB BARS 11-4.21.4, CONTROLS 11- | | 4.21.5, SHOWER UNIT 11-4.21.6, OR CURBS | | 1104.21.7 ARE NOT SHOWN. PLEASE PROVIDE | | DETAILS FOR SHOWER. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|