2003-02-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) RESPONSE NOTED FOR SEPARATE FACILIT-
 IES, BUT DATA ON SHT A-1 STILL CALLS FOR
 EXCEPTION #4. PLEASE CHANGE DATA TO CALL
 OUT FOR EXCEPTION #2 AND INDICATE NUMBER
 OF PEOPLE THAT WILL BE EMPLOYED AS IN-
 DICATED IN SECTION 403.2
 2) RESPONSE NOTED FOR BOTTLED WATER.
 PLEASE SHOW ON PLANS. WATER COOLER SHALL
 BE ARI-1010 COMPLIANT PER 410.1. MANUF.
 INFORMATION REQUIRED.
 3) SHT P-1 VACUUM RELIEF VALVE IS NOT
 FOR THERMAL EXPANSION CONTROL. AN EXPAN-
 SION TANK IS REQUIRED AT WATER HEATER.
 4) SHT A-2 SHOWER DOES NOT COMPLY WITH
 11-4.21.2 ( SHOWER STALL SIZE AND CLEAR
 FLOOR SPACE SHALL COMPLY WITH FIG. 35(A)
 OR (B). NO DETAILS FOR SEAT HEIGHT 11-4.
 21.3, GRAB BARS 11-4.21.4, CONTROLS 11-
 4.21.5, SHOWER UNIT 11-4.21.6, OR CURBS
 1104.21.7 ARE NOT SHOWN. PLEASE PROVIDE
 DETAILS FOR SHOWER.
  