Plan Review Notes For Permit 02120762 |
Permit Number |
02120762 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-02-04 00:00:00 | ************ UNSAT ************ | | | | PLEASE NOTE, SOME NOTED FROM FIRST | | REVIEW, WERE NOT ADDRESSED. | | | | 1)NOTE: PLEASE SEE OCP FOR SERVICE | | ENTRANCE CONDUCTORS TO NEXT HIGHEST | | STANDARD RATING. CONDUCTORS SHOWN ARE | | RATED FOR 285, SERVICE IS SIZED AT 400A | | `S. PLEASE ADJUST. 240-3 | | | | 2)NOTE: PLEASE SEE 250-24, AN EQUIPMENT | | GROUNDING CONDUCTOR IS ONLY INSTALLED | | AFTER FIRST MEANS OF DISC, PANEL DETAIL | | SHOWS A #6 TO PANEL. | | | | 3)NOTE: PLEASE SHOW LOAD CALCUALTIONS | | PER 220-3,-10,-11, -13, ETC. PLEASE SHOW | | W/PER SQ FT, RECEPTS ETC, PLEASE ALSO | | CLARIFY LOAD SHOWN ON 20A OCP FOR TRK | | LIGHTING. SHOWN AT 2500 WATTS WHICH | | EXCEED 80% LOADING OF BRKR. | | | | 4)NOTE: PLEASE SEE SIZING OF OCP FOR | | RTU'S AND AHU PER 424-3 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|