2003-02-04 00:00:00************ UNSAT ************
  
 PLEASE NOTE, SOME NOTED FROM FIRST
 REVIEW, WERE NOT ADDRESSED.
  
 1)NOTE: PLEASE SEE OCP FOR SERVICE
 ENTRANCE CONDUCTORS TO NEXT HIGHEST
 STANDARD RATING. CONDUCTORS SHOWN ARE
 RATED FOR 285, SERVICE IS SIZED AT 400A
 `S. PLEASE ADJUST. 240-3
  
 2)NOTE: PLEASE SEE 250-24, AN EQUIPMENT
 GROUNDING CONDUCTOR IS ONLY INSTALLED
 AFTER FIRST MEANS OF DISC, PANEL DETAIL
 SHOWS A #6 TO PANEL.
  
 3)NOTE: PLEASE SHOW LOAD CALCUALTIONS
 PER 220-3,-10,-11, -13, ETC. PLEASE SHOW
 W/PER SQ FT, RECEPTS ETC, PLEASE ALSO
 CLARIFY LOAD SHOWN ON 20A OCP FOR TRK
 LIGHTING. SHOWN AT 2500 WATTS WHICH
 EXCEED 80% LOADING OF BRKR.
  
 4)NOTE: PLEASE SEE SIZING OF OCP FOR
 RTU'S AND AHU PER 424-3
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW