Plan Review Notes For Permit 02120762 |
Permit Number |
02120762 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-01-06 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 11 | | | | 1) SHT A-1 RESTROOM #118 MINIMUM WIDTH | | FOR HDCP RESTROOM IS 5'3", BUT 5'2" IS | | SHOWN ON PLANS. | | 2) SHT A-1 BLDG. DATA SHOWS 3,700 SQ FT | | SECTION 403.2 REQUIRES 2 FIXTURES UNLESS | | 3000 SQ FT OR LESS. TABLE REQUIRES SEP- | | ARATE FACILITIES FOR MEN AND WOMEN. EACH | | RESTROOM SHALL BE ACCESSIBLE. PLEASE | | SHOW 5' TURNING RADIUS AND CLEAR FLOOR | | SPACE FOR EACH RESTROOM. | | 3) TABLE 403.1 REQUIRES A DRINKING | | FOUNTAIN. ALSO SEE SECTION 410.1. | | 4) SHT P-1 WATER HEATER DETAIL, THERMAL | | EXPANSION PROTECTION REQUIRED PER SECT- | | ION 607.3.2. PLEASE SHOW ON DETAIL | | 5) SHTP-1 DOMESTIC WATER ISOMETRIC, | | WATER HAMMER ARRESTORS REQUIRED BY SEC | | 604.9 SHALL BE LOCATED NEAR THE FIXTURE | | IN AN "EFFECTIVE RANGE" NOT AT THE TOP | | OF THE DROP IN CEILING AS SHOWN. | | 6) DETAIL REQUIRED FOR SHOWER SHOWING | | COMPLIANCE WITH SECTION 11-4.21 AND ALL | | SUBSECTIONS. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|