2002-12-27 00:00:00************* UNSAT *************
  
 1)NOTE: PLEASE CLARIFY/SHOW NEW OR
 EXISTING SHOW WINDOW RECEPTS 210-62
  
 2)NOTE: PLEASE CLARIFY NEW OR EXISTING
 SIGN CIRCUTI PER 600-5
  
 3)NOTE: PLEASE SIZE SERVICE ENTRANCE
 CONDUCTORS PER 310-16/110-14 PLEASE NOTE
 300MCM IS ONLY RATED FOR 285A'S.
  
 4)NOTE: PLEASE VERIFY AND SHOW LOAD
 CALCUALTIONS PER NEC 220. PLEASE NOTE
 TWO LOADS ARE SHOWN. ONE SHOWN EXCEEDS
 300MCM OTHER ??
  
 5)NOTE: PLEASE SHOW TRACK LT CALCUALTION
 S PER 220-12 AND VERIFY TRK. MOST TRK
 IS RATED AT 20A MAX. PANEL SCHEDULE
 SHOWS 25A OCP???
  
 6)NOTE: PLEASE CLARIFY FIRE PUMP AND
 HOW IT IS FED NOW THAT NEW SERVICE IS
 BEING DONE. EVEN IF NO WORK IN AREA,
 PLEASE EXPLAIN WHERE FIRE PUMP IS FED
 FROM..
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372