2002-12-27 00:00:00 | ************* UNSAT ************* | | | | 1)NOTE: PLEASE CLARIFY/SHOW NEW OR | | EXISTING SHOW WINDOW RECEPTS 210-62 | | | | 2)NOTE: PLEASE CLARIFY NEW OR EXISTING | | SIGN CIRCUTI PER 600-5 | | | | 3)NOTE: PLEASE SIZE SERVICE ENTRANCE | | CONDUCTORS PER 310-16/110-14 PLEASE NOTE | | 300MCM IS ONLY RATED FOR 285A'S. | | | | 4)NOTE: PLEASE VERIFY AND SHOW LOAD | | CALCUALTIONS PER NEC 220. PLEASE NOTE | | TWO LOADS ARE SHOWN. ONE SHOWN EXCEEDS | | 300MCM OTHER ?? | | | | 5)NOTE: PLEASE SHOW TRACK LT CALCUALTION | | S PER 220-12 AND VERIFY TRK. MOST TRK | | IS RATED AT 20A MAX. PANEL SCHEDULE | | SHOWS 25A OCP??? | | | | 6)NOTE: PLEASE CLARIFY FIRE PUMP AND | | HOW IT IS FED NOW THAT NEW SERVICE IS | | BEING DONE. EVEN IF NO WORK IN AREA, | | PLEASE EXPLAIN WHERE FIRE PUMP IS FED | | FROM.. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|