2002-12-17 00:00:00GAS PLAN REVIWED FBC 2001, DENIED,PES
 (1) SUBMIT MANUFACTURE SHEETS FOR ALL
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2001
 FUEL GAS CODE SEC. 402.2
 (2) BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 FBC-2001 FUEL GAS CODE SECS 401.8 THRU
 402.5.2 & TABLES 402(1) THRU 402(34).
 (3) SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 (4) SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 GAS CODE.
 END OF COMMENTSPAUL SCHMITZ