Plan Review Notes For Permit 02120666 |
Permit Number |
02120666 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-12-20 00:00:00 | 1) PLEASE INDICATE INTERIOR FINISH | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | 2) PLEASE PROVIDE PRODUCT APPROVAL FOR | | TYPE A DOOR (1000A). NOTES SUGGEST FIRE | | SAFETY ETCHED PATTERN GLASS PANELS. | | | | 3) DOOR SCHEDULE SUGGESTS EXISTING | | LOCKING DEVICES ON EGRESS DOORS. PLEASE | | REVIEW SPECIAL LOCKING ARRANGEMENTS, | | CHAPTER 7, 2000 EDITION OF THE LIFE | | SAFETY CODE. | | | | 4) PLEASE CLEARLY ILLUSTRATE LOCATIONS | | OF EMERGENCY LIGHTING EQUIPMENT WITHIN | | TENANT SPACE. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|