Notes |
Date |
Text |
2002-12-18 00:00:00 | THE VARIOUS FURRED WOOD PANELING | | INSTALLATIONS MUST COMPLY WITH FBC | | 803.9.PROVIDE SPECIFIC METHODS OR | | NOTES, DO NOT REFERENCE THE CODE | | SECTION. | | | | THE RELOCATED DOORS BEING USED WHERE | | FIRE RATED DOORS ARE REQUIRED MUST BE | | LABELED FOR THEIR APPLICATION.ALSO, | | THE CARD READER MUST BE INSTALLED IN | | ACCORDANCE WITH FBC 1012.1.7. | | | | | | THE NOTE ON THE DOOR SCHEDULE "UNDERCUT | | DOORS AS NECESSARY TO CLEAR FLOOR | | FINISHES" CANNOT ARBITRARILY BE APPLIED | | TO FIRE RATED DOORS.SEE NFPA 80-96 FOR | | THE LIMITATIONS RELATIVE TO FLOOR | | SURFACES AND NOTE ON PLANS AS NECESSARY. | | | | PLEASE PROVIDE A FRAMING AND FASTENING | | DETAIL FOR THE SOFFIT CONSTRUCTION | | DEPICTED IN SECTION 4 ON SHEET D901. | | | | THE VINYL AND FABRIC WALL COVERINGS | | MUSTBE LISTED IN ACCORDANCE WITH FBC | | 803.5.2 AS WELL AS THE RELOCATED CARPET. | | | | THE PLANS MUST HAVE THE ARCHITECT'S | | EMBOSSED SEAL AS PROVIDED FOR IN | | CHAPTER 481 OF FLORIDA STATUTES. |
|