Plan Review Notes
Plan Review Notes For Permit 02120627
Permit Number 02120627
Review Stop B
Sequence Number 2
Notes
Date Text
2003-03-05 00:00:00THERE WERE NO STRUCTURAL SPECIFICATIONS
 PROVIDED WITH THE FOUNDATION PERMIT
 APPLICATION.THERE IS NO BUILDING
 PERMIT APPLICATION PENDING.
  
 SHEET S38 OF THE CHM PLANS DATED
 2/17/03CALL OUT AN 18" DIAMETER
 AUGERCAST PILING AS TYPICAL 160 TON/ 80
 TON TENSION TERMINATING AT -36' NGVD.
  
 AS NOTED ON THE 1/23/03 CITY COMMENT
 LIST, THE SOILS ENGINEER RECOMMENDED AN
 18" AUGERCAST PILING TO -50' AND DESIGN
 LOAD OF 80 TONS COMPRESSION AND 30 TONS
 TENSION.HOW DID THE EOR DETERMINE THE
 INCREASED LOADING VALUE AT THE LESSER
 DEPTH?PLEASE PROVIDE YOUR ANALYSIS AND
 STRUCTURAL SPECIFICATIONS NOTING WHAT
 TESTS, STUDIES OR INVESTIGATIONS WERE
 UTILIZED.
  
 AS NOTED ON THE 1/23/03 CITY COMMENT
 LIST, BEFORE A FOUNDATION PERMIT MAY BE
 ISSUED, A BUILDING PERMIT APPLICATION
 MUST BE PENDING, (THERE IS ONLY A $100
 PLAN REVIEW), IMPACT FEES MUST BE PAID
 TO THE COUNTY AND A THRESHOLD INSPECTOR
 PROVIDED.