2002-12-20 00:00:00 | 1) SEVERAL PREVIOUS PLAN REVIEW |
| COMMENTS WHEN THE PLANS WERE SUBMITTED |
| FOR PRELIMINARY PLAN REVIEW HAVE NOT |
| BEEN ADDRESSED. ITEMS 17,19, ON THE |
| LIST MUST BE PROPERLY ADDRESSED BEFORE |
| APPROVAL OF THE FOUNDATION. THESE |
| COMMENTS HAVE BEEN PROVIDED FOR YOUR |
| REVIEW. |
| |
| 2) ELEVATION DRAWINGS DO NOT DISPLAY |
| BUILDING ADDRESS. |
| |
| 3) BUILDING SECTION 3 ON PAGE A6.03 |
| MAKES MENTION OF EIFS. PLEASE BE |
| ADVISED THAT THE CITY LOCAL AMENDMENTS |
| OF THE FLORIDA BUILDING CODE PROHIBITS |
| COMBUSTIBLE TRIM IN THE FIRE LIMITS. |
| |
| 4) STAIR # 1 DOOR WHEN OPENED AT GROUND |
| LEVEL COULD HIT PERSONS WHEN OTHER |
| PERSONS ARE LEAVING THE CORRIDOR. |
| |
| 5) HOW ARE THE UNIT DOORS ON THE |
| EXTERIOR GOING TO BE IDENTIFIED. WILL |
| THEY HAVE THE UNIT NUMBERS ON THEM. |
| |
| 6) HANDRAILS ARE REQUIRED ON ALL STAIRS |
| AND RAMPS. |
| |
| 7) PLEASE ENSURE THAT THE FIRE CONTROL |
| ROOM LOCATED ADJACENT TO THE GRAND |
| LOBBY CAN CONTAIN ALL OF THE REQUIRED |
| DEVICES PER FBC 412.3. |
| |
| 8) THE PHASE ONE CONSTRUCTION OF THE |
| TRANSFORMER VAULT ARE TO MEET ALL |
| APPLICABLE BUILDING AND FIRE CODE |
| REQUIREMENTS. |
| |
| 9) ALL OTHER PREVIOUS COMMENTS ARE |
| TO BE PROPERLY ADDRESSED PRIOR TO |
| RECEIVING APPROVAL FROM FIRE RESCUE |
| TO CONSTRUCT THE BUILDING. ADDITIONAL |
| PLAN REVIEW COMMENTS WILL BE IDENTIFIED |
| AT TIME OF FUTURE REVIEWS. |
| |