2003-01-23 00:00:00 | PLAN REVIEW ONLY NOT A PERMIT |
| APPLICATION. |
| |
| BEFORE A FOUNDATION PERMIT MAY BE |
| ISSUED A PERMIT APPLICATION WITH PLANS |
| AND |
| SPECIFICATIONS FOR THE BUILDING MUST |
| HAVE BEEN APPLIED FOR AND PENDING. |
| |
| BEFORE A PERMIT TO CONSTRUCT IMPACT |
| FEESMUST BE PAID TO THE COUNTY, THE |
| PERMIT |
| PLANS STAMPED BY THAT OFFICE AND A |
| COPYOF THE PAID RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION.CALL 561-233-5025 |
| FOR MORE INFORMATION. |
| |
| SHEET LS 1.02 DOES NOT COMPLY WITH FBC |
| 411.2.4 IN THAT IT SHOWS THE PARKING |
| RAMPS BEING USED FOR EGRESS. |
| |
| SHEET LS 1.00 DEPICTS AN INCORRECT |
| APPLICATION OF FBC TABLE 600.WALL |
| AREA AND THE PERCENTAGE OF ALLOWABLE |
| OPENINGS ARE CALCULATED ON A PER FLOOR |
| BASIS USING INTERIOR HEIGHT OF FINISHED |
| FLOOR TO CEILING IMMEDIATE ABOVE. |
| |
| THE NOTE #8 UNDER RESIDENTIAL TOWER |
| THATREADS IN PART "DISTANCE FROM GLASS" |
| IMPLIES THAT A MEASUREMENT OTHER THAN |
| THE HORIZONTAL DISTANCE FROM A VERTICAL |
| LINE PERPENDICULAR TO THE WALL PLANE |
| WASUSED. |
| INDENTATIONS OR RECESSEDAREAS THAT |
| ARE NOT OPEN TO THE SKY ABOVE ARE |
| CONSIDERED BUILDING AREA.SEE FBC 202 |
| DEFINITIONS FOR "AREA,BUILDING" AND |
| "BUILDING" |
| |
| SHEET LS 1.03 INDICATES A TRAVEL |
| DISTANCE GREATER THAN 75' FROM SOME OF |
| THE UNITS MEZZANINES AND IS PROHIBITTED |
| BY FBC 1005.7.1. |
| |
| SHEET LS 1.03, THE WEST END OF THE |
| GARAGE DOES NOT HAVE TWO EXITS IN |
| ACCORDANCE WITH FBC 1004.2.2. |
| |
| THE HANDICAP PARKING SPACES SHOWN ON |
| SHEET A5.01 ARE REQUIRED TO BE 12' WIDE |
| AND HAVE 98" OF VERTICAL CLEARANCE. |
| SEE FBC 11-4.6.5. |
| |
| WHAT IS THE "STACKED VAULT" USED FOR |
| SHOWN ON SHEET LS 1.04? |
| |
| GIVEN THE ABOVE OBSERVATIONS A |
| FOUNDATION PERMIT IS NOT FEASIBLE AT |
| THIS TIME. |
| |
| THE ARDAMAN SOILS REPORTS RECOMMENDS AN |
| 18" AUGERCAST PILING WITH A DESIGN LOAD |
| OF 80 T COMPRESSION AND 30T TENSION. |
| THE CHM PLANS SHEET S.0, GENERAL NOTES |
| CALLS FOR 160 T COMPRESSION AND 80 T |
| TENSION ON AN 18" AUGERCAST PILING. |
| HOW WAS THE DESIGN LOAD ARRIVED AT?SEE |
| FBC 1809. |