2002-12-09 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THAT THE GROUND CONDUCTORS
 NOTED IN NOTES #4,8,& 12,FROM THE METERS
 TO THE FIRST MEANS OF DISCONNECT CAN
 NOT BE INSTALLED AS THEY WOULD CREATE A
 PARALLEL GROUND PATH WITH THE NEUTRAL.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  