Plan Review Notes
Plan Review Notes For Permit 02120407
Permit Number 02120407
Review Stop M
Sequence Number 1
Notes
Date Text
2002-12-27 00:00:00MECHANICAL PERMIT REQUIRED.PLEASE
 PROVIDE THE FOLLOWING INFORMATION WITH
 MECHANICAL PERMIT APPLICATION.
  
 PERMIT APPLICATION INDICATES REPLACEMENT
 OF 2 AC UNITS & DAMAGED DUCTWORK.
  
 PROVIDE NEW EQUIPMENT INFORMATION,
 INDICATE IF EQUIPMENT WILL BE AN EXACT
 CHANGEOUT.
  
 PROVIDE LAYOUT OF DUCTWORK, IDENTIFY
 NEW & EXISTING.SHOULD RETURN AIR BE
 BE MEANS OF A PLENUM, NO COMBUSTIBLES
 ALLOWED AS PER 2001 FBC(M) 602.2.1.
  
 PROVIDE OUTSIDE AIR CALCULATIONS AS PER
 2001 FBC(M) TABLE 403.3 OR ASHRAE 62-89.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.