Plan Review Notes For Permit 02120308 |
Permit Number |
02120308 |
|
Review Stop |
R |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-01-31 00:00:00 | BUILDING DENIED | | | | 1) A RECORDED COPY OF THE NOTICE OF | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | PERMIT CAN BE ISSUED. | | | | 2) PROVIDE A SOIL TEST FROM A SOIL | | ENGINEER AS REQUIRED BY FBC 1804.2. | | | | 3) THE CONDITIONED AREA LISTED ON THE | | ENERGY CALCS. (3414 SQFT) DOES NOT MATCH | | THE A/C AREA (3101 SQFT) LISTED ON THE | | PLANS. PLEASE CORRECT. | | | | 4)PROVIDE (2) CURRENT AND COMPLETE | | COPIES OF SBCCI OR METRO-DADE PRODUCT | | APPROVALS FOR: | | - SINGLE HUNG WINDOWS | | - ARCHED FIXED GLASS WINDOWS | | NOTE: THE PRODUCT APPROVALS FOR THE ROOF | | TILE EXPIRED ON 12/16/02. | | | | (5) THE HURRICANE PANEL KEY PLAN AND | | INSTALLATION SCHEDULE DOES NOT MATCH THE | | STRUCTURE. THE ONE SUBMITTED IS FOR A | | ONE STORY BUILDING. PLEASE SUBMIT THE | | CORRECT ONES. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)659-8096 EXT.8202 |
|