Plan Review Notes
Plan Review Notes For Permit 02120308
Permit Number 02120308
Review Stop R
Sequence Number 2
Notes
Date Text
2003-01-31 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) PROVIDE A SOIL TEST FROM A SOIL
 ENGINEER AS REQUIRED BY FBC 1804.2.
  
 3) THE CONDITIONED AREA LISTED ON THE
 ENERGY CALCS. (3414 SQFT) DOES NOT MATCH
 THE A/C AREA (3101 SQFT) LISTED ON THE
 PLANS. PLEASE CORRECT.
  
 4)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - SINGLE HUNG WINDOWS
 - ARCHED FIXED GLASS WINDOWS
 NOTE: THE PRODUCT APPROVALS FOR THE ROOF
 TILE EXPIRED ON 12/16/02.
  
 (5) THE HURRICANE PANEL KEY PLAN AND
 INSTALLATION SCHEDULE DOES NOT MATCH THE
 STRUCTURE. THE ONE SUBMITTED IS FOR A
 ONE STORY BUILDING. PLEASE SUBMIT THE
 CORRECT ONES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202