2003-01-10 00:00:00 | BUILDING DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) FL BLD CODE 1804.2.2 QUESTIONABLE |
| SOILS, WHERE THE BEARING CAPACITY IS |
| NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| PROVIDE SOIL REPORT. |
| |
| 3) DRYER VENT CAN NOT PENETRATE THROUGH |
| THE ONE HOUR FIRE RATED WALL ON THE |
| ZERO LOT LINE. TABLE 600 OF THE FBC DOES |
| NOT ALLOW ANY OPENINGS IN A WALL WITHIN |
| THREE FEET OF THE PROPERTY LINE. |
| |
| 4) SECTION 2 ONS1 IS MISLABELED AS 2 |
| ON S2. PLEASE CORRECT. |
| |
| 5) THE USP TA24 CONNECTORS SPECIFIED ON |
| S2 FOR THE TRUSSES AT THE COVERED PORCH |
| AND ON THE BUILDING SECTION ON A4 FOR |
| THE ATTACHMENT OF FLOOR TRUSSES TO THE |
| LEDGER ARE NOT THE PROPER ANCHORS. THESE |
| ARE EMBED TYPE ANCHORS AND NOT WOOD TO |
| WOOD STRAPS. PLEASE CORRECT. |
| |
| 6) PROVIDE ADDITIONAL DETAILS FOR THE |
| WOOD DECK ABOVE THE ENTRY. INDICATE THE |
| CONNECTORS FOR THE 2X10 JOISTS, THE |
| SHEATHING, ROOF COVERING MATERIAL, ETC. |
| |
| 7) THE ENERGY CALCULATIONS ARE REQUIRED |
| TO BE SIGNED BY THE OWNER/AGENT. THE |
| CONDITION SPACE ON THE ENERGY CALC. FORM |
| DOES NOT AGREE WITH THE A/C AREA LISTED |
| ON THE PLANS. PLEASE CORRECT. |
| |
| 8) THE STORM PANEL INSTALLATION |
| SCHEDULE AND KEY PLAN SUBMITTED DOES NOT |
| CORRESPOND TO THIS MODEL. |
| |
| 9) PROVIDE A STRUCTURAL DETAIL FOR THE |
| BOLLARD USED TO PROTECT THE WATER HEATER |
| IN THE GARAGE. |
| |
| 10) PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - SLIDING GLASS DOORS |
| - SINGLE HUNG WINDOWS |
| - ARCHED FIXED GLASS WINDOWS |
| NOTE: PRODUCT APPROVAL FOR ROOF TILE |
| EXPIRED ON 12/16/02. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |