Date |
Text |
2003-01-14 00:00:00 | BUILDING DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) FL BLD CODE 1804.2.2 QUESTIONABLE |
| SOILS, WHERE THE BEARING CAPACITY IS |
| NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| PROVIDE A SOIL BEARING TEST REPORT FROM |
| A LICENSED SOIL ENGINEER. |
| |
| 3) CLARIFY THE DOOR SIZE FOR THE CABANA |
| BATH. IS IT 2-10 OR 2-8 ? |
| |
| 5) SECTION 5 ON S2 SPECIFIES A "USP" |
| HUG 26 CONNECTOR. THIS APPEARS TO BE A |
| HANGER TYPE CONNECTOR, HOWEVER, I COULD |
| NOT LOCATE A HANGER WITH THIS MODEL |
| NUMBER. IS THIS A "USP" HUS HANGER. |
| PLEASE CLARIFY. |
| |
| 6) PROVIDE A DETAIL OF THE WOOD FRAME |
| EXTERIOR BEARING WALLS ON THE SECOND |
| FLOOR. SPECIFY THE CONNECTORS THAT WILL |
| BE USED TO TRANSFER THE LOADS FROM THE |
| TRUSSES TO THE FLOOR GIRDERS. |
| |
| 7) THE ENERGY CALCULATION FORM IS |
| REQUIRED TO BE SIGNED AND DATED BY THE |
| OWNER/AGENT. |
| |
| 8) THE A/C AREA ON THE PLANS IS LISTED |
| AS 3414 SQFT AND THE CONDITIONED SPACE |
| ON THE ENERGY CALCS. IS 3101 SQFT. |
| PLEASE CORRECT. |
| |
| 9) PROVIDE A STRUCTURAL DETAIL OF THE |
| BOLLARD IN THE GARAGE THAT IS PROTECTING |
| THE WATER HEATER. |
| |
| 10) THE INSTALLATION SCHEDULE AND KEY |
| PLAN SUBMITTED ARE NOT FOR THIS MODEL. |
| SUBMIT THE CORRECT ONES. |
| |
| 11) PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - SLIDING GLASS DOORS |
| - STRUCTURAL MULLIONS |
| - OVAL FIXED GLASS WINDOWS |
| - ARCHED FIXED GLASS WINDOWS |
| - DOUBLE OUTSWING FRONT DOORS (THE ONE |
| SUBMITTED IS A PRELIMINARY NOA, THE |
| FINAL ONE WILL HAVE THE RENEWAL STAMP ON |
| THE DRAWINGS AND THE LOGO ON THE COVER |
| SHEET. |
| |
| 12) THE DRYER VENT CAN NOT PENETRATE THE |
| WALL AT THE ZERO LOT LINE. THE FBC TABLE |
| 600 DOES NOT ALLOW ANY OPENINGS WITHIN |
| THREE FEET OF THE PROPERTY LINE. |
| |