Plan Review Notes
Plan Review Notes For Permit 02120294
Permit Number 02120294
Review Stop E
Sequence Number 1
Notes
Date Text
2002-12-24 00:00:00*********** NOTES REDLINED ***********
  
 1) SD NOT PERMITTED IN KITCHEN PER
 NFPA-72 8-1.4.1.6
 2)MISSING EQUIPMENT GROUND BETWEEN MAIN
 AND PANEL. SIZE PER 250-122
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372