Plan Review Notes For Permit 02120294 |
Permit Number |
02120294 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-12-24 00:00:00 | *********** NOTES REDLINED *********** | | | | 1) SD NOT PERMITTED IN KITCHEN PER | | NFPA-72 8-1.4.1.6 | | 2)MISSING EQUIPMENT GROUND BETWEEN MAIN | | AND PANEL. SIZE PER 250-122 | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|