Plan Review Notes
Plan Review Notes For Permit 02120180
Permit Number 02120180
Review Stop R
Sequence Number 1
Notes
Date Text
2003-01-13 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2-PROVIDE SOIL TEST REPORT.
 3-FLOOD ZONE A8: WILL NEED THE ELEVATION
 CERTIFICATE.
 4-CLARIFY DETAIL S21 FOR COLUMN LOCATED
 BETWEEN GARAGE AND STAIRWAY SHOWING
 HOW IS THE STRAP HOLDING THE 2 GIRDER
 TRUSSES. SEC. 104.2.1.2 CITY AMENDMENT
 5-REVISE CONNECTOR TC-1 SPECIFIED ON
 ROOF FRAMING PLAN AT FRONT ELEVATION.
 NEED WOOD TO WOOD CONNECTOR FOR FRAMED
 WALL. SEC. 104.2.1.2 CITY AMENDMENTS.
 6-REVISE STAIR TOP DETAIL ON SHEET A-4
 TO MATCH 2ND FLOOR FRAMING PLAN AND
 SPECIFY FIREBLOCKING AS REQUIRED BY
 SEC. 2305.1.4 FBC 2001.
 7-34SH WINDOW DOESN'T PROVIDE THE 24"
 MIN. CLEAR HEIGHT. ALSO, VERIFY THAT
 24+5 SH WINDOW PROVIDE THE 5.7 S.F.
 MIN. CLEAR OPENING. SEC. 1005.4.4 FBC