2003-01-13 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-PROVIDE COMPLETE INFORMATION FOR STORM | | SHUTTERS UNDER A SEPARATE PERMIT. | | 2-PROVIDE SOIL TEST REPORT. | | 3-FLOOD ZONE A8: WILL NEED THE ELEVATION | | CERTIFICATE. | | 4-CLARIFY DETAIL S21 FOR COLUMN LOCATED | | BETWEEN GARAGE AND STAIRWAY SHOWING | | HOW IS THE STRAP HOLDING THE 2 GIRDER | | TRUSSES. SEC. 104.2.1.2 CITY AMENDMENT | | 5-REVISE CONNECTOR TC-1 SPECIFIED ON | | ROOF FRAMING PLAN AT FRONT ELEVATION. | | NEED WOOD TO WOOD CONNECTOR FOR FRAMED | | WALL. SEC. 104.2.1.2 CITY AMENDMENTS. | | 6-REVISE STAIR TOP DETAIL ON SHEET A-4 | | TO MATCH 2ND FLOOR FRAMING PLAN AND | | SPECIFY FIREBLOCKING AS REQUIRED BY | | SEC. 2305.1.4 FBC 2001. | | 7-34SH WINDOW DOESN'T PROVIDE THE 24" | | MIN. CLEAR HEIGHT. ALSO, VERIFY THAT | | 24+5 SH WINDOW PROVIDE THE 5.7 S.F. | | MIN. CLEAR OPENING. SEC. 1005.4.4 FBC |
|