Plan Review Notes
Plan Review Notes For Permit 02120175
Permit Number 02120175
Review Stop R
Sequence Number 1
Notes
Date Text
2003-01-10 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2-FLOOD ZONE A8: NEED TO PROVIDE THE
 ELEVATION CERTIFICATE.
 3-CLARIFY DETAIL S21 FOR COLUMN LOCATED
 BETWEEN GARAGE AND STAIR WAY SHOWING
 HOW ARE THE TWO GIRDER TRUSSES CONNEC-
 TED TO COLUMN WITH THE STRAP. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 4-REVISE STAIR ENLARGED TOP AREA DETAIL
 ON SHEET A-4 TO MATCH FRAMING PLAN AND
 SPECIFY FIREBLOCKING. SEE SECTION
 2305.1.4 FBC 2001.
 5-REVISE/CLARIFY SIZE OF BEDROOM EGRESS
 WINDOWS. 34SH WINDOW DOESN'T PROVIDE
 THE 24" MIN. CLEAR HT. ALSO, VERIFY
 THAT 24+5 SH WINDOW PROVIDE 5.7 S.F.
 MIN. CLEAR OPENING. SEC. 1005.4.4 FBC.