Plan Review Notes
Plan Review Notes For Permit 02120175
Permit Number 02120175
Review Stop E
Sequence Number 1
Notes
Date Text
2002-12-31 00:00:00********** NOTES REDLINED ********
  
 1)NOTE: PLEASE SEE PANEL SCHEDULE,
 SHOWS 40A OCP ON #10 FOR SUB PANEL.
 CORRELATE W/ RISER,
  
 PLEASE REVISE PLAN AND SUBMIT FOR REVIEW
 BEFORE ROUGH INSPECTION. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372